
Quick answer
The EGC (equipment grounding conductor) carries ground-fault current back to the source so the breaker trips. The GEC (grounding electrode conductor) connects the system to earth through an electrode. The deciding factor is the sizing table: Table 250.122 (breaker rating) for the EGC, Table 250.66 (service conductor) for the GEC. Checked November 2026.
Documenting grounding on a PV permit set?
Book a guided demo and see how SurgePV handles electrical diagrams and bill-of-materials output for a real project.
Book a Free DemoChecking cost first? See the SurgePV pricing page.
SurgePV publishes this page and is a vendor in solar design software. This is a code explainer, so no software products are compared. The table values below follow NEC Tables 250.122 and 250.66 as published in NFPA 70 and were read in November 2026. The edition your authority having jurisdiction (AHJ) has adopted, and any local amendments, govern.
EGC vs GEC: What Is the Difference?
The fastest way to keep these conductors straight is to focus on job function, not appearance. The table below summarizes the core differences that matter on a job site.
| Comparison Point | Equipment Grounding Conductor (EGC) | Grounding Electrode Conductor (GEC) |
|---|---|---|
| Primary job | Carry fault current to trip the breaker or fuse | Connect the system to earth for voltage stability and surge dissipation |
| What it bonds | Module frames, racking, inverter enclosures, conduit, junction boxes | Main service equipment or separately derived systems to grounding electrodes |
| Sizing rule | NEC Table 250.122, based on OCPD rating | NEC Table 250.66, based on largest ungrounded service conductor |
| Normal current | Carries current only during a ground fault | Carries current only during lightning or transient events |
| Typical path | Runs with circuit conductors back to the source | Runs from the grounding bus to ground rods, Ufer, or building steel |
| Continuity rules | Can be spliced with listed methods | Must be continuous or spliced with irreversible methods |
| Common solar application | Array grounding, inverter grounding, AC/DC disconnect grounding | Main service ground, supplementary PV array ground |
A system can have a perfect GEC and still be unsafe if the EGC path is broken. The GEC stabilizes voltage relative to earth, but it does not provide the low-impedance return path that clears a fault. Conversely, a system with a solid EGC and no GEC lacks a stable earth reference and is vulnerable to lightning damage.
What Is an Equipment Grounding Conductor (EGC)?
An equipment grounding conductor is the safety wire for a PV system. It connects all non-current-carrying metal parts back to the grounded conductor at the main service panel. In a solar array, that includes module frames, racking rails, inverter housings, and more. It also covers combiner boxes, disconnect enclosures, and metallic conduit. Proper bonding keeps the entire array at the same electrical potential.
The EGC sits idle during normal operation. It only carries current when a live conductor accidentally touches a metal surface. When that happens, the EGC provides a low-impedance path for fault current to flow back to the source. That high current forces the circuit breaker or fuse to open within milliseconds, removing the hazard before someone can be shocked.
In a properly grounded residential array, a damaged DC conductor may touch a module frame. Fault current then flows through the EGC rather than through a person standing on the roof. The EGC is what makes that possible.
NEC 690.43 requires that all exposed non-current-carrying metal parts of PV systems be grounded in accordance with Article 250. That requirement applies to every system, from a 3kW rooftop installation to a multi-megawatt ground mount. For a deeper look at the article behind these rules, see our NEC Article 690 glossary entry.
Types of EGCs in Solar PV
| EGC Type | NEC Reference | Best For | Caveat |
|---|---|---|---|
| Copper wire EGC | 250.118(1), 250.122 | Most residential and commercial systems | Higher cost than aluminum; best conductivity |
| Aluminum wire EGC | 250.118(1), 250.122 | Long commercial runs where cost matters | Must be larger than copper; needs listed connectors |
| UL 2703 racking as EGC | 690.43(A), UL 2703 | Arrays using listed racking systems | Every clamp and splice must be listed hardware |
| Metal conduit as EGC | 250.118(2)-(5) | EMT, RMC, or IMC raceway runs | Ask the AHJ whether it wants a supplemental wire EGC |
EGC Sizing Example
A typical residential string inverter circuit is protected by a 20A breaker. NEC Table 250.122 requires a minimum 12 AWG copper EGC for that circuit. Many installers standardize on 10 AWG copper because it covers every residential PV circuit up to 60A and reduces field confusion.
For a 100A commercial combiner output, the minimum EGC rises to 8 AWG copper. If the ungrounded conductors are upsized for voltage drop, NEC 250.122(B) requires the EGC to be increased in the same proportion.
What Is a Grounding Electrode Conductor (GEC)?
A grounding electrode conductor connects the grounded conductor or grounding bus at the service equipment to the grounding electrode system. The grounding electrode system is the physical connection to earth. It can include ground rods, concrete-encased electrodes, buried ground rings, metal water pipes, or building steel, depending on what NEC 250.52 recognizes at the site.
The GEC does not clear faults. Its job is to stabilize the system voltage under normal conditions and to give lightning, switching surges, and line-to-earth faults a controlled path into the ground. Without it, the system would float at an unpredictable voltage relative to everything around it.
In a solar installation, the GEC usually runs from the main service grounding bus to one or more ground rods. Some designs also use a supplementary GEC from the PV array disconnect or inverter to the grounding electrode system, as permitted by NEC 690.47.
GEC Sizing Example
A 200A residential service with 2/0 AWG copper service-entrance conductors requires a minimum 4 AWG copper GEC per NEC Table 250.66. If the same service used 4/0 AWG aluminum hots, the minimum GEC would be 2 AWG aluminum or 4 AWG copper. More grounding-system design context is available in our solar PV grounding system design guide.
The GEC is never required to be larger than 3/0 AWG copper or 250 kcmil aluminum, no matter how large the service conductors are. The reason is simple: the earth electrode cannot dissipate more current than those conductors can carry, so a larger wire adds no safety benefit.
Key Differences Between EGC and GEC
The confusion between these two conductors is understandable. They both terminate at the grounding bus. They are often the same color. They both involve the word “ground.” But their design logic is completely different.
| Factor | EGC | GEC |
|---|---|---|
| Purpose | Clear ground faults by tripping OCPDs | Stabilize voltage and dissipate surges to earth |
| Sizing basis | OCPD rating | Largest ungrounded service conductor |
| NEC table | 250.122 | 250.66 |
| Current during normal operation | None | None |
| Current during fault | Fault current until OCPD opens | Transient surge current only |
| Where it runs | With circuit conductors to each piece of equipment | From service equipment to grounding electrode |
| Splices allowed | Listed connectors, crimps, exothermic welds | Must be continuous or irreversibly spliced |
| Material restrictions | Copper, aluminum, or copper-clad aluminum | Same, but aluminum cannot contact earth or concrete |
The most important practical difference is the sizing trigger. An EGC gets larger because the breaker protecting the circuit gets larger. A GEC gets larger because the service-entrance conductors get larger. If you size a GEC like an EGC, you may install a conductor that is too small for the available fault energy. If you size an EGC like a GEC, you may waste money and create installation headaches. Neither outcome improves safety.
How to Size EGC and GEC in Solar PV
Correct sizing is the part of grounding that shows up most often in failed inspections. Both tables are straightforward once you know which one to open.
EGC Sizing per NEC Table 250.122
Minimum EGC size = f(OCPD rating protecting the circuit)Use the rating of the breaker or fuse that protects the circuit conductors, not the ampacity of the conductors themselves.
| OCPD Rating | Minimum Copper EGC | Minimum Aluminum EGC |
|---|---|---|
| 15A | 14 AWG | 12 AWG |
| 20A | 12 AWG | 10 AWG |
| 30A | 10 AWG | 8 AWG |
| 40A | 10 AWG | 8 AWG |
| 60A | 10 AWG | 8 AWG |
| 100A | 8 AWG | 6 AWG |
| 200A | 6 AWG | 4 AWG |
If the ungrounded conductors are increased in size for voltage drop (or similar), NEC 250.122(B) requires the EGC to be increased in proportion to the circular mil area of the upsized conductors. Look up the table value first, then scale it.
GEC Sizing per NEC Table 250.66
Minimum GEC size = f(largest ungrounded service-entrance conductor)Use the size of the largest phase conductor supplying the service or separately derived system.
| Largest Copper Service Conductor | Largest Aluminum Service Conductor | Minimum Copper GEC | Minimum Aluminum GEC |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 AWG | 2/0 or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 or 3/0 AWG | 4/0 or 250 kcmil | 4 AWG | 2 AWG |
| Over 3/0 through 350 kcmil | Over 250 through 500 kcmil | 2 AWG | 1/0 AWG |
| Over 350 through 600 kcmil | Over 500 through 900 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 kcmil | Over 900 through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | Over 1750 kcmil | 3/0 AWG | 250 kcmil |
For parallel service conductors, add the circular mil area of all conductors in each phase and use the equivalent total size to look up the GEC.
Special Sizing Cases
- Ground rod only: If the GEC is the sole connection to a ground rod, pipe, or plate, it does not need to be larger than 6 AWG copper or 4 AWG aluminum.
- Concrete-encased electrode (Ufer): If the GEC is the sole connection to a concrete-encased electrode, it does not need to be larger than 4 AWG copper.
- Aluminum restrictions: Aluminum GECs cannot be in direct contact with masonry or earth per NEC 250.64(A). Use copper for Ufer and direct-buried applications.
Facts from the sizing tables and special cases above, which cite NEC 250.122, 250.66 and 250.64(A).
Buyer Guide: Choosing EGC and GEC Components
The “right” grounding material depends on project size, climate, local amendments, and whether the AHJ accepts aluminum. Use the decision framework below to specify components before the job starts.
Wire Type and Material
| Material | Pros | Cons | Typical Use |
|---|---|---|---|
| Copper | Best conductivity, corrosion resistant, widely accepted | Higher material cost | Residential arrays, corrosive or wet environments, Ufer grounds |
| Aluminum | Lower cost, lighter weight | Larger size required, oxidation risk, termination care | Long commercial feeder runs, cost-driven projects |
| Copper-clad aluminum | Compromise cost and conductivity | Less common, connector availability varies | Mid-size commercial projects |
For most residential solar installations, copper is the safer default. It reduces the chance of an inspector rejecting the installation, holds up better in damp climates, and works with the widest range of listed connectors.
Racking as EGC
If the racking manufacturer has a UL 2703 listing, the racking itself can serve as the EGC. You can then eliminate the separate module-to-module grounding wire. It can remove the module-to-module grounding wire, which saves labor on large arrays.
The catch is that every component in the current path must be part of the listed assembly. Substituting a non-listed clamp, skipping a rail splice bond, or using the wrong torque setting can void the EGC qualification. A wire-type EGC typically still runs from the racking termination point to the grounding bus.
Grounding Electrodes
| Electrode Type | Best For | Notes |
|---|---|---|
| Ground rod | Most residential and retrofit projects | 8 feet long; diameter and listing per NEC 250.52 and 250.53; 6 feet minimum spacing between rods |
| Concrete-encased (Ufer) | New construction with concrete foundations | Excellent low-resistance electrode; 4 AWG copper minimum |
| Ground ring | Commercial and industrial sites | Buried at least 30 inches deep; encircles the building or array |
| Building steel | Commercial buildings with steel framing | Must be effectively grounded; often used as part of the electrode system |
Always check local amendments. Some jurisdictions require two ground rods unless a single rod measures 25 ohms or less. Others mandate Ufer grounds for new construction.
Connectors, Clamps, and WEEBs
Every grounding connection must be made with a listed connector or clamp. Acceptable options include these items:
- Lay-in lugs for busbar terminations.
- Compression connectors for wire-to-wire splices.
- Ground rod clamps listed for the rod and conductor material.
- WEEBs (washer-style electrical equipment bonds) for module-to-rail bonding on some systems.
- Exothermic welds for irreversible GEC splices.
Do not use standard wire nuts, sheet-metal screws, or unlisted hardware for grounding connections. Those are common inspection failures.
Cost Tradeoffs
Copper grounding wire generally costs more per foot than aluminum, but grounding material is a small line in a PV bill of materials. Aluminum can lower the cost of long commercial runs, and only if the AHJ accepts it and the installer uses listed transitions. Pricing for conductors is not published by the code bodies cited here, so get a supplier quote.
The costlier outcome is usually a failed inspection that sends a crew back to the site to pull new wire, add clamps and reschedule.
Common Installation Mistakes and How to Avoid Them
Grounding shows up in inspector findings in more than one country. The Australian Clean Energy Regulator lists PV array earthing among the issues most often found in installations it rated substandard (Inspections Update No. 23). The mistakes below are the ones that come from mixing up the two conductors or their hardware.
Mistake 1: Sizing the GEC From Table 250.122
Some installers treat the GEC like a long EGC and size it from the breaker rating. That produces a conductor that is too small for the service. The GEC must be sized from Table 250.66 based on the largest ungrounded service conductor.
Fix: Before pulling wire, write the service-entrance conductor size on the permit plan and look up the GEC in Table 250.66.
Mistake 2: Sizing the EGC From Conductor Ampacity
The EGC is sized from the OCPD rating, not the ampacity of the circuit conductors. A 20A breaker with 10 AWG circuit conductors still only needs a 12 AWG copper EGC minimum, although many installers upsize to 10 AWG for consistency.
Fix: Mark the breaker rating on the single-line diagram and use Table 250.122.
Mistake 3: Discontinuous GEC
NEC 250.64(C) requires the GEC to be continuous or spliced with irreversible methods such as exothermic welding or compression crimps. A simple wire nut in the GEC path is a code violation.
Fix: Plan the GEC route to avoid splices. If a splice is unavoidable, use a listed irreversible compression connector or exothermic weld.
Mistake 4: Relying on Non-Listed Racking as EGC
Using standard racking hardware as the EGC without a UL 2703 listing is a common shortcut. It works electrically until it does not, and it fails inspection.
Fix: Specify a UL 2703-listed racking system and install it exactly per the manufacturer’s instructions. Keep the listing documentation on site for the inspector.
Mistake 5: Mixing Copper and Aluminum Without Listed Connectors
Connecting copper and aluminum conductors directly causes galvanic corrosion over time. The connection can overheat and fail.
Fix: Use listed bimetallic connectors and anti-oxidant compound rated for the application.
Mistake 6: Running the EGC Outside the Raceway
NEC 300.3(B) requires the EGC to run with the circuit conductors inside the same raceway, cable, or trench. Separating them increases impedance and can prevent the OCPD from opening during a fault.
Fix: Pull the EGC into the same conduit or cable assembly as the phase conductors.
EGC and GEC in Solar Design Software
Modern solar design software should do more than place panels on a roof. It should also document the grounding system in a way that the AHJ can review before the crew arrives on site. That means showing the EGC and GEC on the electrical line diagram, calling out conductor sizes, and noting when racking serves as the EGC.
SurgePV lists electrical workflow support and bill-of-materials output in its product scope (see the SurgePV pricing page). Whether a given tool sizes EGCs or GECs for your jurisdiction is something to see in a demo with your own project, and the responsible engineer or AHJ still approves the design. For how grounding is drawn on plans, see the single-line diagram guide and the grounding system design guide.
Want grounding callouts on your single-line diagrams?
Bring a live project to a SurgePV demo and ask how electrical diagrams and the bill of materials are produced.
Book a Free DemoChecking cost first? See the SurgePV pricing page.
Frequently Asked Questions
What is the difference between EGC and GEC?
An EGC (equipment grounding conductor) carries fault current back to the source so the breaker or fuse trips, while a GEC (grounding electrode conductor) ties the system to earth. They are sized from different NEC tables: Table 250.122 for the EGC and Table 250.66 for the GEC.
Can the same wire serve as both EGC and GEC?
No. NEC 250.121 does not allow an equipment grounding conductor to be used as a grounding electrode conductor. Both may land on the same grounding bus, but each follows its own sizing, routing and continuity rules.
How do you size an EGC for a solar circuit?
Size it from NEC Table 250.122 using the rating of the breaker or fuse protecting the circuit. A 20A device needs 12 AWG copper and a 60A device needs 10 AWG copper. If the circuit conductors are upsized, NEC 250.122(B) requires the EGC to be increased in proportion.
How do you size a GEC for a solar installation?
Size it from NEC Table 250.66 using the largest ungrounded service-entrance conductor. A service with 2/0 AWG copper conductors needs a 4 AWG copper GEC. Where the GEC lands only on a ground rod, 250.66(A) caps the requirement at 6 AWG copper.
Can solar racking replace the EGC?
Racking can act as the array EGC only if it is listed to UL 2703 for that use and installed with its listed bonding hardware. The listing instructions govern, so keep them on site for the inspector.
Is copper or aluminum better for EGC and GEC?
Copper is the simpler default because it needs smaller sizes and is accepted everywhere. Aluminum is allowed for many conductors, but NEC 250.64(A) bars aluminum grounding electrode conductors from direct contact with masonry or earth. Check the AHJ before specifying it.
What is the most common GEC sizing mistake?
Sizing the GEC from the breaker rating (Table 250.122) instead of the service conductor (Table 250.66). The two tables answer different questions, so write the service conductor size on the plan before choosing the GEC.
Sources
Checked November 2026.
- NFPA 70 (National Electrical Code) page: the publisher’s page for the National Electrical Code, which contains Article 250 (Tables 250.122 and 250.66) and Article 690. The code text itself is the primary source for the sizing tables on this page; your adopted edition governs.
- Clean Energy Regulator, Inspections Update No. 23: lists PV array earthing among the issues found in substandard installations in Australia.
- UL 2703 standard listing: covers rack mounting systems, grounding and bonding devices and clamping or retention devices for flat-plate PV modules. Read the racking maker’s own listing documents for the installation rules.
- Related reading on this site: equipment grounding glossary, bonding glossary, NEC Article 690, bonding and grounding for racking.
Last checked: November 2026.

