Back to Blog
solar electrical design14 min read

Solar Lightning Protection: SPDs, LPS & NEC/IEC

Solar lightning protection explained: external LPS, Type 1 and Type 2 SPD selection, DC and AC placement, and where NEC and IEC rules apply.

Keyur Rakholiya

Written by

Keyur Rakholiya

CEO & Co-Founder · SurgePV

Rainer Neumann

Edited by

Rainer Neumann

Editorial contributor · SurgePV

Published ·Updated

Answer

Solar lightning protection works in two layers: an external lightning protection system that intercepts direct strikes, and surge protective devices at DC and AC boundaries that limit induced surges. Per IEC 61643-31, SPDs that pass the Class I test suit highly exposed entry points, while Class II devices handle shorter impulses. Check the adopted standards for ratings and placement.

A strike can destroy inverters, melt connectors, and damage monitoring equipment before the owner knows anything happened. Solar arrays make the exposure worse: they are large, elevated, metal-rich, and tied to long cable runs that behave like antennas.

Last updated: November 2026

Effective protection is not a single product. It is a coordinated system with two layers. The external layer intercepts direct strikes and sends their energy to earth. The internal layer limits induced surges before they reach inverters, monitoring hardware, and switchgear. Most failures happen at the boundary between those layers: the wrong SPD type, missing separation distance, poor bonding, or leads that are too long.

This guide covers both layers for residential, commercial, and utility-scale solar. It explains when an external lightning protection system (LPS) is needed, how SPD types differ, where SPDs go, and which grounding mistakes cause trouble. It does not replace the standards. Numeric ratings, distances, and conductor sizes below are left to the standard and the equipment datasheet on purpose, because they depend on the edition adopted and the product.

Key Takeaway

An SPD does not replace an external LPS, and an LPS does not replace SPDs. Design them as one system, then take every rating and distance from the adopted standard and the manufacturer’s datasheet.

26%
Share of damages attributed to lightning in German statistics quoted by a 2019 PLOS ONE paper (no year given)
1,500 V DC
Upper voltage in the scope of IEC 61643-31:2018 for PV DC SPDs
3 classes
Test classes in IEC 61643-31: Class I, II and III
2024
Year IEC 62305-1 was reissued; the 2010 edition shows a 12 September 2024 withdrawal

Sources: the PLOS ONE paper on PV lightning protection, the IEC 61643-31 webstore listing, and the IEC 62305-1 webstore listing.

In this guide:

  • Why solar arrays are lightning targets, and why induced surges matter
  • The two-layer protection model: external LPS plus internal SPDs
  • How risk assessment decides whether you need an external LPS
  • External LPS components: air terminals, down conductors, earth electrodes
  • SPD types for solar: Type 1, Type 2, and Type 1+2
  • DC-side and AC-side SPD placement
  • Sizing SPDs: Uc, Imax, and Up
  • Grounding, bonding, and separation distance
  • Common installation mistakes
  • Inspection and maintenance

Plan the Array Layout Before the LPS Design

Model the roof in 3D and place the array in SurgePV, so the lightning protection designer works from the real roof geometry.

Book a Demo

Checking cost first? See the SurgePV pricing page.


Why Solar Arrays Are Lightning Targets

Solar arrays combine three features that increase lightning exposure: large horizontal metal area, elevation above surrounding structures, and long conductor runs. A rooftop array is often the highest conductive surface on the building. A ground-mount array can be the highest object across a wide, flat field.

A direct strike carries a very large current for a very short time. No SPD is meant to absorb it alone. A properly designed external LPS with air terminals, down conductors, and a low-impedance earth termination provides the direct-strike current path.

Indirect strikes are a major source of PV damage. When lightning hits the ground or a nearby structure, the resulting electromagnetic field induces high voltages on the DC wiring between modules and the inverter. Long cable runs, large loop areas between positive and negative conductors, and poor shielding all increase the induced voltage.

The damage pattern is familiar to anyone who services PV: bypass diode failure, inverter input-stage damage, melted DC connectors, and fried monitoring equipment. A 2019 PLOS ONE paper on lightning protection for PV systems notes that German statistical data show 26% of damages are caused by lightning. The text gives no year or source for that figure, so treat it as indicative, and use your own site’s lightning data for decisions.

Threat type Source Primary defense
Direct strike Cloud-to-array or cloud-to-nearby structure External LPS (air terminals, down conductors, earthing)
Induced surge Electromagnetic field from a nearby strike SPDs at inverter inputs and outputs and at distribution boards
Ground potential rise Strike current entering earth near the system Bonded earthing, low earth resistance
Grid surge Utility switching or a distant strike on the grid AC SPDs at the service entrance and inverter output

The Two-Layer Protection Model

Solar lightning protection only works when the external and internal layers are designed together. Treating SPDs as a substitute for an external LPS, or the reverse, is a common design error.

Layer 1: External Lightning Protection System (LPS). Intercepts direct strikes, controls the current path down the structure, and dissipates energy into the earth. IEC 62305-3 covers external LPS internationally, and NFPA 780 covers it in the United States.

Layer 2: Internal Surge Protection. Uses surge protection devices (SPDs) at zone boundaries to limit transient overvoltages on power and communication circuits. IEC 62305-4 covers protection of electrical and electronic systems within structures. IEC 61643-31 covers SPDs on the DC side of PV installations, and the NEC includes surge protection provisions in the United States.

The coordination concept comes from lightning protection zones (LPZ). Each zone has a defined electromagnetic environment, and you install protection suited to the threat at each boundary:

  • LPZ 0A: Direct exposure. Full lightning current and unattenuated field, such as the open air above the array.
  • LPZ 0B: Protected against direct strikes by the LPS, but still exposed to the electromagnetic field.
  • LPZ 1: Inside the building shield, with partial current and an attenuated field. DC cables enter the structure here.
  • LPZ 2 and beyond: Further attenuated zones near sensitive equipment.

A Type 1 SPD is commonly placed at the LPZ 0 to 1 boundary and a Type 2 SPD at the next boundary, so the energy is managed in stages rather than dumped on one device.


When Lightning Protection Is Required

The trigger for an external LPS is a risk assessment, not guesswork. IEC 62305-2 provides the formal method, and NFPA 780 takes a different approach in the United States. Both start with the local lightning ground flash density.

Lightning density varies a great deal by region, so use data for the actual site rather than a national average. The IEC 62305-2 assessment compares the calculated risk against a tolerable level and considers:

  • Collection area of the structure and array
  • Local ground flash density
  • Type of construction and roofing material
  • Occupancy and consequence of damage
  • Presence of sensitive electronic systems

Small residential systems in low-lightning regions may not need a dedicated external LPS where the building already has adequate protection, while commercial and industrial systems often do, and insurers may ask for one. In the United States, NFPA 780 is not automatically adopted everywhere, and some jurisdictions require it only for certain building categories. Ask the authority having jurisdiction and the insurer which edition and scope apply.

IEC 62305-1 was reissued in 2024, and the 2010 edition shows a withdrawal date of 12 September 2024 on the IEC webstore. Confirm which edition of the IEC 62305 series your project is specified to.

For India-specific compliance, see the detailed guide from Heaven Green Energy. India’s CEA safety regulations include solar provisions on lightning and overvoltage protection, so check the current text for your project.


External Lightning Protection System Components

An external LPS has four elements, and each must be designed as a continuous, low-impedance path.

Air Terminals

Air terminals intercept the descending lightning leader. Two types are common on solar projects:

  • Franklin rods: Simple vertical metal points placed above the highest point of the array. Their protection area is set by the protection level and the method in the standard.
  • Early Streamer Emission (ESE) terminals: Active devices marketed with a larger protection radius. ESE systems follow NF C 17-102, and acceptance varies by jurisdiction, so confirm the authority accepts them.

For small residential arrays, a single rod above the highest panel corner may be enough where the risk assessment supports it. For larger arrays, designers use a mesh of air terminals or terminals sized to cover the array footprint.

The rolling sphere method is one way to place air terminals. A sphere whose radius corresponds to the protection level is rolled over the structure, and any point it touches needs air terminal coverage. The radius for each protection level comes from the IEC 62305 series, so take it from the edition in force.

Down Conductors

Down conductors carry strike current from the air terminal to the earth electrode. The practical rules are consistent across the standards:

  • Keep them short and direct. Every bend adds inductance.
  • Use conductors sized for impulse current, with the material and cross-section taken from IEC 62305-3 or NFPA 780 as applicable.
  • Provide enough down conductors for the structure and array, as the LPS designer specifies.
  • Provide a test point for resistance testing.
  • Make joints with methods the standard accepts, such as welded or exothermic connections, not simple clamps.

Earth Termination

The earth termination dissipates strike current into the soil. A ring electrode around the structure is generally preferred over a single rod, because a ring or multiple electrodes spread current, reduce ground potential rise, and lower overall resistance. In rocky or high-resistivity soil, ground enhancement material or other electrodes may help. The target resistance and electrode layout come from the standard and the LPS designer.

Equipotential Bonding

Metallic parts in the zone of the LPS must bond to the equipotential bonding network. This includes PV module frames, racking, cable trays, inverter enclosures, and AC equipment. Bonding prevents dangerous voltage differences during a strike. Conductor sizes are set by the standard.


SPD Types for Solar: Type 1, Type 2, and Type 1+2

SPDs are classified by the test they pass. IEC 61643-31, which covers SPDs for the DC side of PV installations, describes three test classes. Its introduction says Class I tests simulate partial conducted lightning current impulses, and SPDs that pass the Class I test are generally recommended for locations of high exposure, such as line entrances to buildings protected by lightning protection systems. SPDs that pass the Class II or Class III tests face shorter impulses.

Type 1 SPD

Type 1 SPDs are rated for partial lightning current. The key parameter is the impulse discharge current (Iimp). They suit points of high exposure, such as cables entering a building that has an external LPS, or where separation distance cannot be maintained.

Type 2 SPD

Type 2 SPDs are rated against shorter impulses that represent induced surges from nearby strikes and switching. IEC 61643-31 defines the nominal discharge current (In) as the crest value of an 8/20 current, and the maximum discharge current (Imax) as a crest value with an 8/20 waveshape set by the manufacturer, which is equal to or greater than In. Type 2 devices are the usual choice for inverter DC inputs, inverter AC outputs, and distribution boards.

Type 1+2 SPD

A Type 1+2 device combines both capabilities in one housing. It is a practical choice when an external LPS exists but space is limited at the combiner box or service entrance, and it can simplify retrofits.

Type 3 SPD

Type 3 devices protect sensitive terminal equipment such as monitoring gateways and communication lines. Check the datasheet before using any SPD on a DC power circuit, because it must be rated for that circuit.

SPD type Purpose Typical solar location
Type 1 Partial direct-strike current Highly exposed entry points, service entrance with an LPS
Type 2 Induced surges and switching Inverter DC input, inverter AC output, distribution board
Type 1+2 Combined Space-constrained combiner boxes, retrofits
Type 3 Residual surges at sensitive equipment Monitoring and communications lines

SPD Placement Rules for DC and AC Sides

Placement is as important as device selection. An SPD with long leads can perform worse than a smaller SPD with short, direct leads.

DC-Side Placement

Array combiner box. Add a DC SPD at the combiner output when the cable run to the inverter is long. Many designers use a cable-length rule of thumb for this, and the exact threshold comes from the standard and the SPD manufacturer. Where an external LPS exists, the SPD at that location is typically a Type 1+2 device, as the design specifies.

Inverter DC input. Grid-connected inverters need DC-side protection at the input terminals. Keep the total lead length to the SPD and to the earth reference as short as the manufacturer allows, because every extra length of lead adds inductance and raises the voltage the equipment sees.

String-level protection. Large ground-mount projects sometimes specify string-level SPDs. This is a project decision, not a general rule.

AC-Side Placement

Inverter AC output. A Type 2 AC SPD belongs near the inverter AC output, with a voltage rating suited to the system voltage. Read the datasheet for the continuous operating voltage and the permitted system types.

Main distribution board. If the solar sub-panel feeds a main board at a different location, add another SPD at that board and follow the manufacturer’s rules for distance and coordination between the two.

Service entrance. Recent NEC editions include a surge protection requirement for services in Section 230.67. Check the scope and the edition your jurisdiction has adopted. This is separate from the solar-specific SPD design.

Configuration Modes

The SPD configuration depends on the DC earthing system of the inverter:

  • Floating (IT) systems, common with transformerless inverters: protect all conductors against earth and against each other, as the SPD manufacturer specifies.
  • Functionally earthed systems: use the protection modes the manufacturer lists for that earthing arrangement.
  • High-resistance earthed systems: check the SPD’s leakage current against the insulation monitoring device, to avoid false alarms.

Pro Tip

Twist the positive and negative SPD leads together to cut loop inductance. If the inverter terminal block is far from the earth bar, run a short dedicated earth conductor to the nearest bonding point rather than routing SPD earth leads through long conduit.


Sizing SPDs: Uc, Imax, and Up

Maximum Continuous Operating Voltage (Uc)

A frequent sizing error is choosing the continuous operating voltage from the nominal operating voltage instead of the maximum open-circuit voltage at the coldest site temperature. Module Voc rises as temperature drops. IEC 61643-31 defines the maximum continuous operating voltage for PV application (UCPV) as the maximum DC voltage that may be continuously applied to the SPD’s mode of protection. An SPD whose UCPV is too low for the cold-weather string voltage will conduct continuously, heat up, and fail.

Step one is the cold-corrected string voltage. Take the module open-circuit voltage at standard test conditions, multiply by the modules in series, and correct for the lowest site temperature using the temperature coefficient in the datasheet.

Illustrative example (assumed inputs):

  • String: 20 modules, Voc(STC) per module = 41.5 V
  • String Voc(STC) = 20 x 41.5 V = 830 V
  • Temperature coefficient of Voc = 0.28% per degree C (use the datasheet value)
  • Lowest site temperature = -10 degrees C, so the change from 25 degrees C is 35 degrees
  • Cold-corrected Voc = 830 V x (1 + 0.0028 x 35) = 830 V x 1.098 = about 911 V

Step two is the margin and the rating. The SPD’s UCPV must exceed that cold-corrected voltage by the margin required in the standard and by the manufacturer. IEC 61643-32 addresses selection and application of PV SPDs, so check it, and choose the next suitable rating from the manufacturer’s catalog.

Discharge Current Rating (Imax and In)

Choose In, Imax, and Iimp from the site’s lightning risk and the zone where the device sits. Higher-risk sites with an external LPS call for Type 1 or Type 1+2 devices at exposed boundaries, while low-risk sites may need only Type 2 devices. The risk assessment and the manufacturer’s selection guide give the values, so do not copy a rating from another project.

Voltage Protection Level (Up)

Up is the voltage the SPD presents at its terminals during a surge. IEC 61643-31 defines it as the maximum voltage expected at the SPD terminals for an impulse of defined steepness and discharge current, and it is declared by the manufacturer. Compare Up against the equipment’s impulse withstand voltage in the inverter datasheet, keep a margin as the standard requires, and remember that lead length adds to the voltage the equipment actually sees.


Grounding, Bonding, and Separation Distance

Earth Electrodes for LPS and Electrical Systems

Practice differs by standard and region. Some national practices keep lightning earth electrodes physically separate from electrical earth electrodes and bond them at one point, while IEC 62305-3 sets its own requirements for the earth termination. Follow the standard adopted for the project and the LPS designer’s drawings, and document the bonding. Whatever the layout, a bonded system avoids dangerous potential differences between lightning and electrical earths during a strike.

Separation Distance Between LPS and PV System

Separation distance prevents dangerous sparking between the external LPS and internal metallic installations. IEC 62305-3 gives the calculation, which uses factors that depend on the protection level, the current distribution among down conductors, the insulating material, and the length from the nearest bonding point. Take those factors from the edition in force rather than from a summary.

If the required separation distance cannot be maintained, the LPS designer specifies bonding of the PV frame and DC cabling to the LPS at the point of proximity, or SPDs at that point.

Module Frame and Racking Bonding

All PV module frames, racking, and cable trays must bond to the equipotential bonding network. Use fittings designed for the racking material, such as serrated washers on aluminum with anti-oxidant compound where the manufacturer specifies. See the glossary entry on equipment grounding for the fundamentals.

For a complete walkthrough of solar grounding design, see the guide on solar PV grounding system design. For racking-specific bonding, see bonding and grounding solar racking.


Common Installation Mistakes

Mistake Consequence Correct practice
Using an AC SPD on the DC side An AC device is not built for DC arc extinction; fire risk Use only SPDs rated for PV DC circuits
Choosing Uc from nominal voltage SPD conducts on cold mornings and can fail thermally Use the cold-corrected string voltage plus the required margin
Long SPD leads Voltage at the equipment rises and protection is wasted Keep leads short and direct, within the manufacturer’s limit
Poorly bonded LPS and electrical earths Strike current backflows toward the inverter ground Bond per the standard and document it
Missing separation distance Sparking between the LPS and the array frame Maintain it, or bond and add SPDs at proximity
Wrong protection modes on floating DC Some conductors left unprotected Use the modes the manufacturer lists for the earthing system
No backup overcurrent protection A failed SPD can draw follow current Coordinate with upstream protection per the SPD datasheet and overcurrent protection coordination
Ignoring SPD status after storms A failed SPD stays in place and the next surge hits the inverter Inspect or replace after any confirmed lightning event

The most expensive mistake is using an AC-rated SPD on the DC side. When its protective element fails under DC fault current, the arc may not extinguish and the enclosure can overheat.

Further Reading

For SPD standards and failure modes in more depth, read the guide on surge protection devices for solar PV.


How Solar Design Software Helps

Lightning protection design needs accurate data that is often guessed in the field: array geometry, roof dimensions, obstructions, and where equipment sits. Cloud solar design software gives the lightning protection designer a 3D roof model and array layout to work from, and bill-of-materials output to carry into the specification.

SurgePV covers roof modeling, layout, and shading analysis in one workflow. Outputs support design and documentation, but they do not replace approval by the responsible engineer, authority, or insurer, and they do not calculate an LPS or select SPD ratings. Cable lengths, minimum site temperature, and the SPD selection stay with the electrical designer and the standards.


Maintenance and Inspection

Lightning protection is not install-and-forget. SPDs degrade with surge events, and earth connections change with soil moisture and corrosion.

Task What to check When
SPD status Visual status window, or remote contact if fitted Each maintenance visit, and after any known strike
Earth connections Resistance and condition per the LPS standard On the standard’s schedule
Bonding connections Tightness and corrosion On the standard’s schedule, and after the first year of service
Air terminals and down conductors Damage, corrosion, and joints On the standard’s schedule
Replace SPDs After a failed status or as the manufacturer directs Immediately

For commercial systems, specify SPDs with remote status outputs and wire them into the monitoring platform, so a silent failure becomes an alarm. Residential systems rely on visual status windows, so include the check in every maintenance visit.

Document the Layout Your Engineer Will Protect

Keep roof geometry, array layout, and equipment locations in one SurgePV project, then share the drawings with your lightning protection and electrical designers.

Book a Demo

Need the proposal side? See solar proposal software or pricing.

Three actions before your next solar lightning protection design:

  • Run the IEC 62305-2 risk assessment using the actual site ground flash density and array collection area. Do not rely on regional averages.
  • Coordinate the external LPS and internal SPDs as one system, with Type 1 or Type 1+2 devices at exposed boundaries and Type 2 devices at inverter terminals, as the design specifies.
  • Bond the lightning and electrical earths as the standard requires, and document earth measurements at commissioning. Check SPD status on every maintenance visit.

Frequently Asked Questions

Do solar panels attract lightning?

Not on their own, but arrays are exposed because they are large, metallic, elevated, and connected to long cables. They can be a direct-strike target, and their wiring can pick up induced surges from nearby strikes. A risk assessment under IEC 62305-2 decides whether an external LPS is needed, and SPDs handle induced surges.

What is the difference between Type 1 and Type 2 SPD for solar?

Type 1 SPDs pass the Class I test, which simulates partial conducted lightning current, and suit highly exposed points, such as line entrances to buildings with a lightning protection system. Type 2 SPDs pass tests with shorter impulses and protect against induced surges. IEC 61643-31 describes these test classes for the DC side of PV installations.

Where should SPDs be placed in a solar PV system?

Place SPDs at the DC input of the inverter, the AC output of the inverter, and the service or distribution board, and add DC SPDs at the array end when cable runs are long. Keep SPD leads as short as the manufacturer allows. Check the adopted standard and the SPD datasheet for exact placement rules.

How do you size a solar SPD voltage rating?

Start from the maximum string open-circuit voltage at the lowest site temperature, using the module temperature coefficient. The SPD’s continuous operating voltage for PV (UCPV) must exceed it with the margin the standard and manufacturer require. IEC 61643-32 addresses selection, so check it and the datasheet before choosing a rating.

Is a lightning protection system mandatory for solar installations?

It depends on the jurisdiction, building, and risk assessment. IEC 62305-2 provides the risk method, NFPA 780 covers lightning protection systems in the United States, and the NEC includes surge protection provisions for services. India’s CEA safety regulations include solar provisions on lightning and overvoltage protection. Check the editions your authority has adopted.

What is separation distance in lightning protection?

Separation distance is the clearance needed between the external lightning protection system and internal metallic parts, so a strike cannot cause dangerous sparking. IEC 62305-3 gives the calculation and its factors. If the distance cannot be kept, the LPS designer specifies bonding or other measures.

How often should lightning protection and SPDs be inspected?

Follow the lightning protection standard’s maintenance schedule and the SPD manufacturer’s instructions, and inspect after any known strike. Check SPD status indicators, bonding connections, earth connections, and air terminals. Replace SPDs that show a failed status or that the manufacturer says to replace after a surge.

Where this fits

This article is part of SurgePV's Solar Design hub, which works through the topic from first principles to the decisions a project team actually has to make.

About the Contributors

Author
Keyur Rakholiya
Keyur Rakholiya

CEO & Co-Founder · SurgePV

Keyur Rakholiya is identified by SurgePV as its CEO and a company co-founder. His SurgePV author page lists only role information that can be tied to the public profile below; credentials, project totals, testing claims, media appearances, and speaking engagements are not asserted without retained evidence.

Editor
Rainer Neumann
Rainer Neumann

Editorial contributor · SurgePV

Rainer Neumann is credited as an editorial contributor on SurgePV content. This profile does not assert engineering credentials, project totals, software-testing experience, education, speaking engagements, or media citations because independent verification evidence is not retained in the publication record.

Get Solar Design Tips in Your Inbox

Join 2,000+ solar professionals. One email per week - no spam.

No spam · Unsubscribe anytime

Book Free Demo

Choose which optional technologies SurgePV may use. Essential storage remains active for security and requested features.