Answer
Size the backfeed breaker at 125% of the inverter's maximum continuous output current, rounded up. Then apply the 120% busbar rule (2020 NEC): 125% of inverter current plus the main breaker must not exceed 120% of busbar rating. A 200 A panel with a 200 A main allows a 32 A inverter and 40 A breaker.
On a 200 A panel with a 200 A main breaker, the busbar leaves room for only a 40 A solar breaker. That one number decides how large an inverter you can connect without changing the panel. Last updated: November 2026.
A backfeed breaker is the breaker that feeds solar power back into your main panel. This guide shows how to size it, how to check the 120% rule, and where the DC side differs. NEC is the National Electrical Code, the US wiring code. The permit office that checks your plans is called the authority having jurisdiction, or AHJ. It decides which NEC edition applies to you.
Quick Reference: Inverter Output Current to Minimum Breaker Size
The table uses the output current in one maker’s data sheet. Multiply by 1.25 and round up to the next standard breaker size. The data is from the SMA Sunny Boy-US data sheet. We use it as an example only. Read the data sheet for your own inverter.
| Inverter | AC power at 240 V | Max output current at 240 V | Min breaker at 240 V | Max output current at 208 V | Min breaker at 208 V |
|---|---|---|---|---|---|
| Sunny Boy 3.0-US | 3,000 W | 12.5 A | 20 A | 14.5 A | 20 A |
| Sunny Boy 3.8-US | 3,840 W | 16.0 A | 20 A | 16.0 A | 20 A |
| Sunny Boy 5.0-US | 5,000 W | 21.0 A | 30 A | 24.0 A | 30 A |
| Sunny Boy 6.0-US | 6,000 W | 25.0 A | 35 A | 25.0 A | 35 A |
| Sunny Boy 7.0-US | 7,000 W | 29.2 A | 40 A | 32.0 A | 40 A |
| Sunny Boy 7.7-US | 7,680 W | 32.0 A | 40 A | 32.0 A | 40 A |
Arithmetic for each row: 12.5 x 1.25 = 15.6 A, 14.5 x 1.25 = 18.1 A, 16.0 x 1.25 = 20.0 A, 21.0 x 1.25 = 26.3 A, 24.0 x 1.25 = 30.0 A, 25.0 x 1.25 = 31.3 A, 29.2 x 1.25 = 36.5 A, 32.0 x 1.25 = 40.0 A. Each result is rounded up to the next standard breaker size. Use the maximum output current from the data sheet, not the power divided by the voltage.
- Sunny Boy 3.0-US12.5 A
- Sunny Boy 3.8-US16 A
- Sunny Boy 5.0-US21 A
- Sunny Boy 6.0-US25 A
- Sunny Boy 7.0-US29.2 A
- Sunny Boy 7.7-US32 A
Source: SMA Sunny Boy-US data sheet (SBxx-US-DS-en-41), used as an example only, checked November 2026.
How Do You Size a Solar Backfeed Breaker?
SMA’s guidance is to multiply the inverter’s maximum output current by 125% and round up to the standard breaker size (SMA blog, 2015). That post cites NEC 2014 sections 690.8(A)(3), 690.9(B) and 240.6(A). Section numbers change between editions, so check the one your AHJ enforces.
- Find the inverter’s maximum continuous AC output current on its data sheet.
- Multiply it by 1.25.
- Round up to the next standard breaker size.
- Check the 120% busbar rule (next section).
- Ask your AHJ which NEC edition it enforces and what it needs on the plans.
Worked example: 7.68 kW inverter on a 200 A panel
Take the Sunny Boy 7.7-US. The data sheet gives 7,680 W and a maximum output current of 32.0 A at 240 V.
- Breaker size: 32.0 A x 1.25 = 40.0 A. The standard size is 40 A.
- Busbar check: 1.25 x 32.0 A = 40 A. Add the 200 A main breaker: 40 + 200 = 240 A.
- The limit is 120% of the 200 A busbar: 1.20 x 200 = 240 A.
- 240 A is not more than 240 A, so the design passes with no room to spare.
Key Takeaway
On a 200 A busbar with a 200 A main breaker, a 7.7 kW inverter uses all of the allowed 240 A. A larger inverter, or a second source on the same panel, fails the check.
Catch busbar limits before the permit set
See how electrical workflow support and a bill of materials fit into a SurgePV design.
Book a DemoChecking cost first? See the SurgePV pricing page
Mayfield Renewables uses the same numbers for a 32 A inverter on a 200 A panel (Code Corner, 2023).
How Does the 120% Rule Work?
The 120% rule limits how much solar a panel’s busbar can take. The busbar is the metal bar inside the panel that carries power to the breakers. Mayfield Renewables quotes the 2020 NEC text, section 705.12(B)(3):
- Option 1: the sum of 125% of the power source output current and the rating of the overcurrent device protecting the busbar must not exceed the busbar rating. If it passes, the solar breaker can go anywhere on the bus.
- Option 2, the “120% rule”: when the two sources are at opposite ends of the busbar, that same sum can reach 120% of the busbar rating. The busbar must be sized for its loads under Article 220.
- Label: with Option 2, a permanent warning label must sit on the panel. It reads “Warning: Power source output connection - do not relocate this overcurrent device.”
Why the opposite ends? Mayfield explains that when the main breaker and the solar breaker sit at opposite ends, the currents do not add up anywhere along the bus. The overcurrent device protecting the busbar is usually the main breaker.
The 2023 and 2026 editions of the NEC may use different section numbers and words. NFPA says the code panels are reorganizing the NEC, with more changes in the 2026 edition (NFPA 70 page). Read the edition your AHJ enforces.
Largest solar breaker by panel size
With Option 2, the largest solar breaker is 1.20 x busbar rating - main breaker rating. The largest inverter output current is that number divided by 1.25. These are example panels. Check your own panel label.
| Busbar | Main breaker | Largest solar breaker | Largest inverter output current |
|---|---|---|---|
| 100 A | 100 A | 1.20 x 100 - 100 = 20 A | 20 / 1.25 = 16 A |
| 125 A | 125 A | 1.20 x 125 - 125 = 25 A | 25 / 1.25 = 20 A |
| 200 A | 200 A | 1.20 x 200 - 200 = 40 A | 40 / 1.25 = 32 A |
| 225 A | 200 A | 1.20 x 225 - 200 = 70 A | 70 / 1.25 = 56 A |
| 200 A | 150 A | 1.20 x 200 - 150 = 90 A | 90 / 1.25 = 72 A |
| 400 A | 400 A | 1.20 x 400 - 400 = 80 A | 80 / 1.25 = 64 A |
What if the 120% rule fails?
You have a few options. Choose a smaller inverter. Ask your AHJ whether a different main breaker size fits your real loads. Or ask your utility and AHJ about another connection point. Each option has its own code rules and utility rules, and we do not cover them here. Ask before you finalize the plans.
Pro Tip
Check the busbar before you quote the inverter. Write the busbar rating, the main breaker rating and the inverter’s maximum output current on the site survey sheet, then run both the 125% and 120% checks. It is far cheaper to pick a smaller inverter on paper than to fail plan review.
Check the electrical side while you design
Walk through a sample project from layout to wiring and parts list in a guided SurgePV demo.
Book a Free DemoNot ready for a call? Read the SurgePV pricing page
How Do You Size Breakers on the DC Side?
DC breakers and fuses protect the circuits between the modules and the inverter. Two sources give slightly different advice, so check both and your module data sheet:
- Mayfield Renewables (quoting the 2023 NEC): the maximum circuit current is the module short-circuit current (Isc) x 1.25. Overcurrent devices are then sized at 125% of that value, and the same 125% step applies to conductors. Together that is 1.25 x 1.25 = 1.56, often called the “156% factor” (Mayfield, November 2024).
- Silfab Solar’s installation manual says to multiply Isc by 125% to size the overcurrent device, and use 156% of Isc for conductor sizing. It also says the device must not exceed the series fuse rating in the module data sheet (Silfab manual). It lists 20 A, 25 A or 30 A, depending on the module series.
The two sources do not agree on the device rating. Local electrical code takes precedence, as the Silfab manual also says. Use the module’s maximum series fuse rating as the upper limit, and ask your AHJ.
Use devices that are marked for the type of current in their circuit, AC or DC. Read the listing on the device label before you buy.
Which Mistakes Fail Plan Review?
- Using power divided by voltage. Use the maximum output current from the data sheet.
- Skipping the 125% step. The breaker would be too small.
- Leaving out the 125% in the busbar check. The sum must include 125% of the inverter output current, not only the breaker rating.
- Putting the solar breaker in the wrong place. For Option 2 it goes at the opposite end of the bus from the main breaker, with the label.
- Putting an AC-only device in a DC circuit. Check the listing.
- Going above the module’s maximum series fuse rating. It is printed in the module data sheet.
Where Does Design Software Help?
SurgePV supports 3D roof modeling, array layout, shading analysis, energy-yield modeling, financial modeling, electrical workflow support, bill-of-materials output and proposal generation. See how that fits your projects in a guided demo. For string and combiner devices, read our OCPD sizing guide. For fuses, read our solar fuse sizing guide. For wire, see solar wire sizing under NEC 690.8.
To see these checks inside a design workflow, book a SurgePV demo or read about solar design software. Also read about the NEC 2026 rapid shutdown rules and AC disconnect sizing.
Frequently Asked Questions
How do you size a breaker for a solar inverter output circuit?
Multiply the inverter’s maximum continuous AC output current by 1.25 and round up to the next standard breaker size. For an inverter with a 32.0 A maximum output current, 32.0 x 1.25 = 40.0 A, so use a 40 A breaker. Then check the 120% busbar rule.
What is the 120% rule for solar backfeed breakers?
In the 2020 NEC, 705.12(B)(3)(2) says that when the two sources are at opposite ends of the busbar, 125% of the source output current plus the busbar’s protective device rating must not exceed 120% of the busbar rating. A label is also required.
What size solar breaker fits a 200 A panel with a 200 A main breaker?
The largest is 1.20 x 200 - 200 = 40 A. That fits an inverter with a maximum output current up to 32 A, because 32 x 1.25 = 40 A.
Why does the busbar check include 125% of the inverter current?
The 2020 NEC text, as Mayfield Renewables quotes it, adds 125% of the source output current to the protective device rating. A shortcut you may see is main breaker + solar breaker at most 120% of the busbar. It gives the same answer when the solar breaker is exactly 125% of the inverter current, as in the 32 A example. Use the text of the edition your AHJ enforces.
What if the 120% rule fails?
Choose a smaller inverter, or ask your AHJ and utility about other options. Each option has its own code and utility rules. Ask before you finalize the plans.
How do you size a breaker for a single solar string?
Sources differ. Mayfield Renewables, quoting the 2023 NEC, sizes the device at 125% of the maximum circuit current, which is 1.25 x 1.25 x Isc. Silfab’s manual says 125% of Isc. Do not exceed the series fuse rating in the module data sheet, and ask your AHJ.
Can I use an AC breaker in a DC solar circuit?
Only if the device is marked for DC at that voltage. Read the listing on the device label and the manufacturer’s instructions.
Where this fits
This article is part of SurgePV's Solar Design hub, which works through the topic from first principles to the decisions a project team actually has to make.


