Back to Blog
solar policy27 min read

NEC 2026 Solar Changes: Article 690 Updates

NEC 2026 solar changes for Articles 690, 705 and 706, including engineer-calculated currents, 705.20 disconnects, line-side limits and storage rules.

Keyur Rakholiya

Written by

Keyur Rakholiya

CEO & Co-Founder · SurgePV

Rainer Neumann

Edited by

Rainer Neumann

Editorial contributor · SurgePV

Published ·Updated

Answer

NEC 2026 changes solar design rules in Articles 690, 705 and 706. It removes the 100 kW limit on engineer-calculated PV voltage and current, points PV and storage disconnects to 705.20, reinstates the 2020 line-side conductor length limits, and deletes 706.16. It applies only where your jurisdiction has adopted it, so confirm the edition with the AHJ.

Last updated: November 2026

SurgePV publishes this post and sells solar design software.

The 2026 edition of the National Electrical Code (NFPA 70) changes several rules that solar designers use every day, mostly in Articles 690, 705 and 706. This guide follows the Mayfield Renewables summary of the 2026 NEC updates, written by an engineer who served on Code Making Panel 13, and it flags the claims you may see elsewhere that the summary does not list. If your team still designs to NEC 2023, the changes below are the ones to check before your next permit submission.

TL;DR: NEC 2026 Solar Changes

NEC 2026 drops the 100 kW size limit on engineer-calculated PV voltage and current, adds a new 690.8 method that uses module instructions, points PV and storage disconnects to 705.20, reinstates the 2020 line-side conductor length limits in 705.11(C)(1), and deletes 706.16 so most backup storage falls under Article 702. It applies only where your jurisdiction has adopted it.

Check conductor and current sizing before you submit

Build the electrical design from the module datasheet values, then review the string and circuit assumptions against the code edition your AHJ enforces.

Book a Demo

Checking cost first? See the SurgePV pricing page.

100 kW
Former size limit on engineer-calculated PV voltage and current, removed in 2026
0.5
Fractions of an ampere or volt below this are dropped in final calculations (690.4(G))
3
Articles with PV and storage changes in this guide: 690, 705 and 706
2020
Edition whose line-side conductor length limits return in 705.11(C)(1)

Source for the figures above: Mayfield Renewables summary of the 2026 NEC updates, published 26 January 2026. They are changes the summary describes, not a count of every 2026 revision.

NEC 2026 Solar Changes: Quick Reference Overview

The table lists the PV and storage changes described in the Mayfield summary. Section numbers follow that summary, so check the final text of NFPA 70 (2026) for the wording before you cite them in a permit package.

NEC section Change Design impact
690.4(G) Fractions below 0.5 are dropped in final calculations, after correction factors are applied Gives one rounding method for AHJ review
690.7(A)(3) and 690.8(A)(1)(a)(3) Engineer-calculated maximum voltage and current no longer limited to systems over 100 kW ac Any system size can use the method
690.8(A)(1)(a)(2) New method allows maximum circuit current from instructions included with the PV module Can help with bifacial modules when makers publish instructions
690.13 PV system disconnecting means now points to 705.20 One reference for disconnect requirements
705.11(C)(1) Conductor length limits from the 2020 Code are reinstated Line-side templates need a length check
705.20 Serves as the disconnect reference for 690.13 and 706.15 Same requirements across PV and storage
706.15 Disconnecting means refers to 705.20 Storage aligns with PV disconnect rules
706.16 Deleted Most backup storage falls under Article 702 optional standby
702.4 New third sizing option for one- and two-family dwellings; inverter-based systems use a listed power control system Affects residential storage sizing
Article numbering Article 220 is now Article 120, and Article 750 is now Article 130 Update references in templates

The 2026 cycle has fewer sweeping changes than 2020 or 2023, but the line-side length limits and the 706.16 deletion will still cause permit questions if templates are not updated.

Article 690 Updates: The Solar PV Sections Designers Must Review

Article 690 covers solar PV systems. The 2026 changes here mostly make calculation rules clearer, with one real change to who may use engineer-calculated values.

Section 690.4(G): Rounding Rule for Calculations

NEC 2026 adds a rule for fractions of an ampere or volt: fractions below 0.5 are dropped. The Mayfield summary says only final calculations, after correction factors and conditions of use have been applied, may be rounded up or down.

The sequence: apply temperature correction, conduit fill adjustment and any other condition of use, then round the final value. Do not round intermediate steps. Setting this out in the calculation sheet answers the question before a plan reviewer asks it.

Pro Tip: Show the Rounding Order

List the correction factors in the order you applied them and state that rounding happens once, on the final value. A reviewer who sees the sequence can check it in seconds, and you avoid a resubmittal over a half-ampere.

Sections 690.7 and 690.8: The 100 kW Limit Is Gone

Under NEC 2023, the engineer-calculated method for maximum PV voltage and current was limited to systems over 100 kW ac. The Mayfield summary reports that the 2026 NEC removed the reference to a system size, so the calculation method is allowed for any size system. In practice this method relies on a licensed engineer’s calculation, and tools such as the NREL System Advisor Model are one way engineers model irradiance and temperature effects.

Whether it pays off is a project question. An engineer’s fee and stamp are a cost, and the saving depends on the conductor run length and how far the calculated current sits below the prescriptive 1.25 multiplier result. Get a quote for the calculation, size the conductors both ways, and compare the totals.

Section 690.8(A)(1)(a)(2): Module Instructions as a Calculation Method

NEC 2026 adds a new subsection that allows the maximum circuit current to be calculated using instructions included with the PV module. Mayfield notes this may help with bifacial modules if manufacturers provide such instructions, since rear-side current is otherwise hard to account for.

The practical steps are simple. For each bifacial module on your approved list, read both the datasheet and the installation manual. If the manual gives a calculation method or a higher current value, record which source you used and attach the relevant pages to the permit package. If the manual says nothing, size from the datasheet short-circuit current as before.

Worked example (illustrative numbers, not a specific module). Suppose a datasheet lists Isc = 13.8 A and the installation manual states a maximum current of 15.1 A for bifacial operation. Two strings in parallel give 27.6 A from the datasheet value and 30.2 A from the manual value, a difference of 2.6 A that could change the conductor or overcurrent device size. Which value governs depends on the method you are allowed to use, so confirm with the AHJ and the code text.

For panel selection and layout, see our bifacial solar panel design guide.

Section 690.13: Disconnecting Means Point to 705.20

NEC 2026 revises 690.13 to direct designers to install the PV system disconnect in accordance with 705.20. The Mayfield summary says it also reorders the requirements and refers to 110.25 for locking, and the author expects the practical requirements to stay essentially unchanged. Because 706.15 also points to 705.20, one section now sets the disconnect rules for PV and storage. For related sizing guidance, see AC disconnect sizing for solar.

Article 705 Changes: Line-Side Interconnection Rules Are Back

Article 705 covers interconnected power production sources, meaning how PV connects to the utility service. NEC 2026 has fewer subsections in 705.11 than the 2023 edition and relies more on cross-references to other articles for overcurrent protection, disconnecting means and grounding and bonding.

Section 705.11(C)(1): Conductor Length Limits Reinstated

Section 705.11(C)(1) returns the conductor length limits from the 2020 Code that the 2023 Code removed. The Mayfield summary stresses that these distances are the actual conductor lengths, not the physical distance between components. That matters for any project using a supply-side (line-side) connection, which taps between the utility meter and the service disconnect and is common where the main panel is full.

The limits themselves are in the code text, so read 705.11(C)(1) in NFPA 70 (2026) and copy the lengths and conditions from there into your template notes. Do not rely on a figure quoted in a blog post, including this one.

What to do with an existing template. Measure the conductor path in the layout, not the straight line between boxes, and compare it with the limit for the building type. If a design runs longer, the options are to shorten the run, change the interconnection point, or use the protection the code allows for longer runs.

Key Takeaway: Audit Line-Side Templates First

The reinstated limits in 705.11(C)(1) are the change most likely to affect existing design templates. Check every standard line-side detail against the code text before you submit in a jurisdiction that has adopted NEC 2026.

Section 705.20: One Disconnect Reference

Section 705.20 is now the reference for disconnecting means used by 690.13 and 706.15. The Mayfield summary says the requirements mirror those in the 2023 version of 690.13. For projects with both PV and storage, check with the AHJ whether one disconnect can serve more than one source in your configuration, and confirm its rating and marking against 705.20.

Article 706 and Article 702: Energy Storage Changes

Solar-plus-storage is now a large share of new residential work in many US markets, and the 2026 changes affect how storage is classified and sized.

Section 706.15: Disconnecting Means

Section 706.15 now refers to 705.20 and to its own subsections (A) through (D), which makes disconnect requirements consistent across technologies. For AC-coupled and DC-coupled systems, cite the same disconnect section for the PV and storage parts of the permit package. See AC-coupled vs DC-coupled battery solar for detail.

Section 706.16: Deleted

Section 706.16, Connection to Energy Sources, is deleted in the 2026 edition. The Mayfield summary says that without it, most energy storage systems used for backup loads fall under optional standby systems in Article 702 instead of Article 710, so sizing uses 702.4, Capacity and Rating.

Section 702.4: A Third Sizing Option for Dwellings

Mayfield also describes a new third sizing option in 702.4 that applies only to one- and two-family dwellings. Inverter-based systems must use a listed power control system (PCS), and the summary cites UL 3141 as the basis for applying the section. A power control system limits the current an inverter-based source can deliver, so the code can size the connected equipment to the controlled limit.

If you design storage regularly, ask your main AHJs how they are handling the reclassification and whether they have updated submittal checklists. Check Article 702 and your AHJ’s amendments before you assume a particular review path.

Keep the electrical design and the permit set in step

Review string layouts, bill-of-materials output and electrical workflow in one project, so a code change means updating one model, not a stack of documents.

Book a Demo

Checking cost first? See the SurgePV pricing page.

Article Renumbering: What Moved

The Mayfield summary notes a structural change that is not PV specific: Article 220 is now Article 120, and Article 750 is now Article 130. Any template, calculation sheet or checklist that cites the old numbers will need updating, even if the content you rely on is unchanged. Record the NEC edition together with the section number on every sheet, because the same number can mean a different rule in a different edition.

Claims You May See Elsewhere: Check the Code Text

Some summaries of NEC 2026 list changes that the Mayfield article does not cover. They may be right or wrong, and this guide does not repeat them as fact. If you see one of these in a vendor article, read the code text before you change a design standard.

Claim seen in other summaries What to do
New arc flash labeling content in 110.16 (voltage, boundary, incident energy or PPE, assessment date) Read 110.16 in NFPA 70 (2026) and compare it with your 2023 labels
A new Article 270 for medium-voltage grounding and bonding Check the 2026 article list and the grounding rules your project falls under
Listed cable ties, and written intermateability documentation for connectors Check the installation and equipment listing requirements, and follow the connector makers’ instructions
Flexible conductors at tracker articulation points Follow the tracker manufacturer’s approved wiring methods and the code sections for flexible cords and cables
A separate 66 foot outer limit on line-side runs Read 705.11 and do not design to a figure you have not seen in the text
Rapid shutdown (690.12) changes The Mayfield summary does not describe any; see our NEC 2026 rapid shutdown guide

Arc flash is worth a note on its own. Where a project has labeling or study requirements, they usually rest on an engineering study done under a recognized method such as IEEE 1584, and the study cost depends on the system. Ask an engineer for a quote and scope it at proposal stage.

Manufacturer Instructions and the Code

Equipment instructions and the code are separate documents. The new 690.8(A)(1)(a)(2) method lets a module’s own instructions feed one calculation, but it does not turn manufacturer instructions into a way around other code rules. If an instruction conflicts with the code requirement for your edition, design to the code requirement, record the conflict, and ask the manufacturer to clarify in writing.

For design teams, the practical step is to read the installation manual for each product you specify, check wire sizing, disconnect placement, grounding method and connector type against the code edition in force, and keep the pages you relied on in the project file.

State Adoption Timelines: When NEC 2026 Actually Applies to Your Projects

NFPA publishes a new NEC edition every three years, and states adopt it on their own schedules, often with amendments. A published edition is not the same as an enforced edition. Designing to the wrong edition causes permit rejections that delay projects and cost money.

What to check Where to check it
The edition your state has adopted The NFPA NEC adoption map as a starting point, then the state agency
Local amendments The AHJ’s permit portal or building department
The effective date for new applications The AHJ, in writing if possible
Whether the AHJ accepts a newer edition early The AHJ’s plan review team

The only authoritative source is your local AHJ. Do not assume NEC 2026 applies because NFPA has published it, and do not assume NEC 2020 applies just because your state has not announced adoption of 2023 or 2026.

Key Takeaway: Put the Code Edition on the Cover Sheet

Include the applicable NEC edition on every permit package cover sheet. In jurisdictions that enforce an older edition, do not apply 2026-only rules, such as the reinstated line-side length limits, without confirming local adoption.

How to Update Your Solar Design Process for NEC 2026

The changes above turn into a short checklist for design teams.

1. Audit line-side templates. Check the conductor path length in every supply-side connection detail against 705.11(C)(1) in the edition your AHJ enforces.

2. Update the bifacial current source. For each bifacial module on your approved list, pull the datasheet and installation manual, record which value or method you used, and attach the pages.

3. Decide when to use engineer-calculated values. Now that the size limit is gone, compare the engineer’s fee against conductor savings on a few typical projects, so you have a rule of thumb.

4. Point disconnect details to 705.20. Update PV and storage disconnect notes in your templates and keep the rating and marking information current.

5. Update storage permit documentation. For solar-plus-storage projects in 2026 jurisdictions, cite Article 702 and the 702.4 sizing option where it applies, and ask the AHJ about submittal checklists.

6. Update article numbers. Replace references to Article 220 and Article 750 with the new numbers where you cite the 2026 edition.

7. Verify the unlisted claims. For the items in the table above, read the code text before changing a standard.

8. Confirm the enforceable edition with each AHJ. Build this into your project intake checklist, and record the confirmed edition and the date of confirmation.

Capable solar design tools help because they hold electrical inputs in one project, so a change to a circuit assumption flows through the layout and bill of materials. The generation and financial tool can show the cost effect of conductor sizing choices when you compare design paths.

Our solar safety compliance checklist covers the pre-permit inspection process alongside these updates.

NEC 2026 vs NEC 2023: Side-by-Side Comparison

Topic NEC 2023 NEC 2026 (per Mayfield summary)
Line-side conductor length 2020 limits removed 2020 limits reinstated in 705.11(C)(1), measured as actual conductor length
Engineer-calculated PV voltage and current Limited to systems over 100 kW ac Size limit removed
Maximum circuit current method Standard calculation New option to use instructions included with the PV module
PV disconnecting means 690.13 with its own requirements 690.13 points to 705.20
Storage disconnecting means Own requirements 706.15 refers to 705.20
Storage classification 706.16 present 706.16 deleted; most backup storage under Article 702
Dwelling storage sizing Existing options New third option in 702.4 with a listed power control system
Calculation rounding No stated method Fractions below 0.5 dropped in final calculations
Article numbering Article 220 and Article 750 Now Article 120 and Article 130

What Future Code Cycles Mean for Solar Designers

Each cycle moves section numbers, and the 2026 renumbering of Articles 220 and 750 is a reminder. Permitting software, design templates and compliance checklists that hardcode section numbers need a review whenever a new edition is adopted. Keep the edition and the section together in every citation, and keep a short log of which templates were updated for which edition.

How Solar Design Software Reduces NEC 2026 Compliance Risk

Manual checking on every permit package is slow and easy to get wrong. Design software helps when it keeps the electrical inputs in the same project as the layout, so you catch inconsistencies before the permit set is built.

SurgePV’s published scope covers 3D roof modeling, array layout, shading analysis, energy-yield modeling, financial modeling, electrical workflow support, bill-of-materials output and proposal generation. Results depend on the inputs, equipment models and review you apply, and outputs support documentation but do not replace approval by the responsible engineer or the authority having jurisdiction. Use solar design software for layout and bill-of-materials, shadow analysis for irradiance inputs, and the generation and financial tool to compare design paths.

Bifacial Modules and Circuit Current: What Drives the Rear-Side Contribution

Rear-side current depends on the surface under and around the array, the mounting height, the row spacing, the tilt and the time of day. A white roof membrane or light gravel returns more light than dark asphalt, and a raised ground mount sees more of the reflected light than a flush roof mount. That is why a single front-side Isc value can understate what a bifacial module may carry in a bright, reflective setting, and why module makers are the right source for a method. Our guide on bifacial gain by mounting type explains how these factors interact.

For design teams, the useful habit is to record the assumed surface, mounting height and row spacing next to the current value you used. If an inspector asks why you chose a number, the answer is on the calculation sheet.

How to Read the Code Text Without Relying on a Summary

Summaries, including this one, can drift from the final wording. A short method keeps a design standard safe:

  1. Find the section in the licensed NFPA 70 (2026) text, through your NFPA subscription or the free-access reading copy on the NFPA 70 page.
  2. Read the section together with the definitions and any exceptions it cites.
  3. Compare it with your 2023 template line by line, and write the difference in one sentence.
  4. Ask the AHJ whether it has an interpretation or a local amendment.
  5. Date the change log entry and name who verified it.

Worked Example: Source Circuit Current Before Correction Factors

This worked example uses illustrative module numbers, not a specific product, to show how a higher published current moves the sizing. It uses the 1.25 multiplier that the prescriptive method applies to short-circuit current, and it stops before temperature and conduit fill adjustments, which depend on the installation.

Step Datasheet value used Installation manual value used
Module short-circuit current (Isc) 13.8 A 15.1 A
Multiplied by 1.25 for source circuit current 17.25 A 18.9 A (rounded from 18.875)
Two strings in parallel (twice the single-string value) 34.5 A 37.8 A
Difference 3.3 A

The point is not the exact number. A difference of about 1.6 A per string can push a design across a conductor or overcurrent device size boundary. That is why 690.8(A)(1)(a)(2) matters for bifacial modules: if the maker publishes a method or value in the instructions, you need to know which one your AHJ will accept before you finalize the bill of materials. The rounding rule in 690.4(G) applies to the final calculated value, so keep the unrounded numbers until the last step.

Line-Side Interconnection: Options When a Run Is Too Long

If a measured conductor path is longer than the 705.11(C)(1) limit allows, there are a few standard ways to respond. Each has a cost and a review consequence, so compare them before you change a template.

Option What it involves Trade-off
Shorten the run Move the tap point or the overcurrent device closer together May need a utility or panel-location change
Change the interconnection point Use a load-side connection where the busbar and breaker space allow Limited by panel rating and the busbar rules
Add a new service-side enclosure Place the overcurrent device where the run is short Extra equipment and labor
Use the protection the code allows for longer runs Follow the code text for the conditions that apply Needs engineering review and AHJ acceptance

Do the measurement at layout stage. A conductor path measured on a drawing is easy to correct, while one found at inspection means rework on a finished site.

What to Put in the Permit Package for an NEC 2026 Project

A complete package makes the plan review faster and answers the usual questions before they come back as comments.

  • Cover sheet: the NEC edition, the AHJ’s confirmed adopted edition and the date of confirmation
  • Calculation sheet: the correction factors in the order applied, the rounding step, and the source of each current value
  • Module documents: the datasheet pages and, for bifacial modules, the installation manual pages that you relied on
  • Single-line diagram: the interconnection point, the conductor lengths for any supply-side connection, and the disconnect locations with ratings
  • Storage documents: the classification path (Article 702 or other), the sizing option, and the listing for any power control system
  • Equipment list: listing and labeling information for each product

Questions to Ask Your AHJ

Question Why it matters
Which NEC edition do you enforce for applications submitted today? Sets every other answer
Do local amendments change Articles 690, 705, 706 or 702? Local amendments override the model code
How do you measure supply-side conductor length for 705.11(C)(1)? Avoids a disagreement at inspection
Do you accept the module-instructions method in 690.8(A)(1)(a)(2)? It depends on the reviewer and the instructions provided
How do you review storage under Article 702 now that 706.16 is deleted? Review checklists are still being updated
Do you want engineer-calculated values stamped for small systems? Sets the cost of the calculation method

Conclusion

NEC 2026 is a consolidation update, but it asks for action in a few places:

  • Reinstated line-side length limits mean auditing every supply-side design template against the code text
  • The removed 100 kW limit and the new module-instructions method mean updating how you document PV current calculations, especially for bifacial modules
  • The deleted 706.16 and the new 702.4 option change the permit path for solar-plus-storage projects
  • Renumbered articles mean updating references in templates and checklists
  • Local adoption decides when any of this applies, so confirm the enforceable edition with each AHJ

To keep design, bill of materials and permit documents aligned on your next project, book a SurgePV demo and walk through the workflow.

Frequently Asked Questions

What are the biggest NEC 2026 changes for solar installations?

The Mayfield Renewables summary highlights the removal of the 100 kW limit on engineer-calculated PV voltage and current, a new 690.8 method that uses module instructions, disconnects pointing to 705.20, reinstated line-side conductor length limits, and the deletion of 706.16. Check the code text for exact wording.

When does NEC 2026 take effect for solar projects?

It takes effect only where your state or local jurisdiction has adopted it. NFPA publishes a new edition every three years, but adoption schedules and local amendments differ, so confirm the enforced edition and effective date with the AHJ before you design.

What is the conductor length limit for line-side solar connections in NEC 2026?

Section 705.11(C)(1) reinstates the conductor length limits from the 2020 Code. Mayfield notes the distances are actual conductor lengths, not the physical distance between components. Read the lengths and conditions in the 2026 code text rather than relying on a figure quoted in an article.

Do bifacial solar panels require different calculations under NEC 2026?

NEC 2026 adds 690.8(A)(1)(a)(2), which allows maximum circuit current to be calculated using instructions included with the PV module. Mayfield says this may help with bifacial modules if manufacturers provide instructions. Read the datasheet and installation manual, and record the method you used.

Is the 100 kW limit for engineer-calculated PV currents still in NEC 2026?

No. Under NEC 2023 the engineer-calculated method for maximum PV voltage and current was limited to systems over 100 kW ac. Mayfield reports the 2026 edition removed the system size reference, so the method can apply to any size system, with a licensed engineer’s calculation.

How does NEC 2026 affect energy storage systems paired with solar?

Section 706.16 is deleted, so most storage used for backup loads falls under optional standby systems in Article 702. Section 706.15 now refers to 705.20 for disconnects, and 702.4 adds a third sizing option for one- and two-family dwellings that uses a listed power control system.

Did NEC 2026 change the article numbers solar designers cite?

Yes, in part. Mayfield notes that Article 220 is now Article 120, and Article 750 is now Article 130. Update templates and calculation sheets that cite the old numbers, and record the NEC edition together with the section number.

Where this fits

This article is part of SurgePV's Solar Incentives & Policy hub, which works through the topic from first principles to the decisions a project team actually has to make.

About the Contributors

Author
Keyur Rakholiya
Keyur Rakholiya

CEO & Co-Founder · SurgePV

Keyur Rakholiya is identified by SurgePV as its CEO and a company co-founder. His SurgePV author page lists only role information that can be tied to the public profile below; credentials, project totals, testing claims, media appearances, and speaking engagements are not asserted without retained evidence.

Editor
Rainer Neumann
Rainer Neumann

Editorial contributor · SurgePV

Rainer Neumann is credited as an editorial contributor on SurgePV content. This profile does not assert engineering credentials, project totals, software-testing experience, education, speaking engagements, or media citations because independent verification evidence is not retained in the publication record.

Get Solar Design Tips in Your Inbox

Join 2,000+ solar professionals. One email per week - no spam.

No spam · Unsubscribe anytime

Book Free Demo

Choose which optional technologies SurgePV may use. Essential storage remains active for security and requested features.