SANS 10142-1:2020 is the foundation of every solar electrical installation in South Africa. It is not a solar-specific standard — it is the national wiring code that applies to all electrical installations — but it includes provisions specifically for PV power supply systems. Getting SANS 10142-1 compliance right determines whether your installation passes the CoC inspection and satisfies network operator requirements.
This guide focuses on the SANS 10142-1 requirements most relevant to solar PV: DC wiring, protection, earthing, labelling, and the PV-specific provisions that inspectors check.
DC Circuits Are Live Whenever There Is Light on the Panels
Unlike AC circuits that can be de-energised by switching off a breaker, DC solar circuits remain live as long as sunlight falls on the array. SANS 10142-1 requires isolation means that can safely interrupt the DC current — not just open-circuit it. Ensure DC isolators are rated for the DC break capacity of the system, not just the DC voltage.
SANS 10142-1 Structure for Solar Installers
SANS 10142-1:2020 is a comprehensive standard that covers all types of electrical installation. For solar PV installers, the most relevant sections are:
| Section | Relevance |
|---|---|
| General principles | Fundamental safety requirements applicable to all installations |
| Cable and conductor sizing | DC string cables, AC output cables — ampacity and derating |
| Protection against overcurrent | String fusing, DC circuit breakers, AC protection |
| Protection against earth faults | Earthing system design, RCD requirements |
| Earthing and bonding | Array structure, inverter chassis, cable armouring |
| Special installations — PV systems | DC circuit requirements, isolation, surge protection specific to PV |
| Inspection and testing | What the CoC inspection covers |
DC Cable Requirements
Cable Type
Standard twin-and-earth or single-core PVC cables are not appropriate for solar DC applications. The correct cable types for DC solar string wiring:
| Cable Type | Application | Notes |
|---|---|---|
| PV1-F (or H1Z2Z2-K) | String wiring, panel-to-combiner | UV-resistant, double-insulated, rated for outdoor exposure |
| Armoured DC solar cable | Underground DC runs | Steel wire armouring for mechanical protection |
| Standard singles in conduit | Protected DC runs in buildings | PVC singles are acceptable inside conduit, away from UV exposure |
Cable Sizing
Size DC cables for:
- The module’s Isc × 1.25 as the design current for the cable
- Temperature derating based on installation method (free air, in conduit, clipped to surface, bundled)
- Maximum voltage drop (typically 1% for DC strings to limit power loss)
- The maximum DC system voltage — check cable insulation rating is adequate
DC Overcurrent Protection
SANS 10142-1 and the PV-specific provisions require overcurrent protection in the DC circuit under certain conditions:
| Condition | Required Protection |
|---|---|
| Single string, single inverter input | String fuse not required (Isc cannot exceed cable rating) |
| Two strings in parallel at combiner | String fuses required to prevent reverse current from exceeding cable rating |
| Three or more strings in parallel | String fuses required |
| Main DC cable from combiner to inverter | DC circuit breaker or fuse protecting the main DC cable |
DC fuses and breakers must be rated for DC use. The voltage rating must exceed the maximum DC system voltage. AC-rated devices have fundamentally different arc interruption characteristics and are not safe in high-voltage DC solar applications.
Earthing and Bonding Requirements
Array Structure Earthing
The PV mounting structure is exposed metal that could become live under fault conditions. SANS 10142-1 requires:
- All metal rail sections to have electrical continuity (verified by conductance testing)
- The bonded structure to be connected to the main earth of the premises
- The earth conductor to be sized to handle the fault current that could flow
In practice, most aluminium mounting systems achieve conductivity through the mounting hardware — verify with the manufacturer that their hardware provides rated electrical continuity or install supplementary bonding conductors.
Transformerless Inverters and Array Floating
Transformerless string inverters are common in South Africa. These inverters have no galvanic isolation between the DC and AC sides. SANS 10142-1 and inverter manufacturer requirements typically prohibit grounding either the positive or negative DC bus in transformerless inverter installations. The array is left “floating” with respect to earth. This is acceptable — and typically required — for transformerless inverters, but it affects the earthing design.
Labelling Requirements
| Label Required | Location | Content |
|---|---|---|
| DC cable marking | DC cables throughout installation | ”SOLAR PV DC SUPPLY” or equivalent |
| DC isolator warning | On or adjacent to DC isolator | ”PV ARRAY — DC SUPPLY — DO NOT OPEN UNDER LOAD” |
| Main distribution board warning | At main DB | Warning that a PV system is connected |
| Emergency shutdown label | Near main isolator | Shutdown procedure reference |
| String circuit labels | At string combiner | String number, source circuit identifier |
Labels must use durable materials appropriate for the installation environment. Adhesive labels in wet or high-temperature areas (cavity roofs) must be rated for the temperature and humidity range.
Produce SANS 10142-1-Compliant Solar Documentation
SurgePV generates the single-line diagrams, cable schedules, and protection device schedules that DoL inspectors check during CoC inspections — all formatted for South African SSEG applications.
Explore the Design ToolNo commitment required · 20 minutes · Live project walkthrough
Common SANS 10142-1 Non-Compliances Found at Inspection
| Non-Compliance | Typical Cause |
|---|---|
| String fuses missing where required | Installer skipped protection design step |
| DC cable not UV-rated for exposed runs | Standard building cable used on rooftop |
| Array structure not bonded to earth | Assumed mounting hardware provided continuity without testing |
| DC isolator not rated for DC break | AC-rated isolator installed on DC circuit |
| Labels missing or illegible | Labels not installed or applied after weathering |
| AC isolator not lockable | Standard domestic isolator used instead of lockable version |
| No surge protection where specified | SPD specified in design but not installed |
Frequently Asked Questions
Is SANS 10142-1 the same as IEC 60364? SANS 10142-1 is South Africa’s national adaptation of the IEC 60364 series. It adopts most IEC 60364 requirements with South African modifications. For solar PV, the relevant IEC 60364 part is IEC 60364-7-712 (PV power supply systems), which is incorporated into SANS 10142-1.
Who can purchase SANS 10142-1? SANS 10142-1:2020 is available for purchase from the South African Bureau of Standards at sabs.co.za. The standard is not freely available online. Practicing solar electrical contractors should purchase and maintain access to the current edition.
Does a battery storage addition require a new CoC? Yes. Adding a battery storage system to an existing solar installation is a material change to the electrical installation. A new or amended Certificate of Compliance is required after the battery addition. The battery wiring, protection, and earthing must all meet SANS 10142-1 requirements.
See the Certificate of Compliance guide, the DoL vs ECSA sign-off guide, and the full South Africa compliance overview. Use solar design software to generate compliant system documentation.