🇺🇸 United States Tool 9 min read

Solar Fuse & Breaker Sizing: NEC 690.9 OCPD Calculator Guide

Size overcurrent protection devices (fuses and breakers) for solar PV strings and combiners per NEC 690.9. Learn the 125% rule, when OCPD is required vs. omitted, DC-specific equipment requirements, and combiner box fuse sizing.

Rainer Neumann

Written by

Rainer Neumann

Content Head · SurgePV

Keyur Rakholiya

Reviewed by

Keyur Rakholiya

CEO & Co-Founder · SurgePV

Published ·Last reviewed ·Regulator: NFPA / National Electrical Code (NEC)

NEC 690.9 requires overcurrent protection for solar PV circuits — and the specific equipment requirements matter. Standard AC breakers are not allowed in DC circuits. The 125% sizing rule applies. And combiner box fuses have their own selection criteria.

Why DC OCPDs Are Different

DC fault current behaves differently than AC. In an AC circuit, current crosses zero 120 times per second — at each crossing, the arc temporarily extinguishes and can be interrupted by the breaker. In a DC circuit, current is steady — there’s no natural zero crossing.

A standard AC breaker can’t interrupt DC fault current at the voltages and currents in a solar system. The arc would sustain, potentially burning through the breaker. DC-rated fuses and breakers use different internal designs to interrupt DC arcs.

All OCPDs in PV source and output circuits must be:

  • Specifically listed for DC operation
  • Rated for the DC voltage of the circuit
  • Rated for the DC current level

The 690.9 Sizing Rule

Minimum OCPD rating = 1.25 × Maximum circuit current
Circuit Isc× 1.25Minimum OCPDStandard Fuse Size (next up)
8.0A10.0A10.0A10A
9.0A11.25A11.25A12A or 15A
9.58A11.975A11.975A12A or 15A
10.0A12.5A12.5A15A
11.0A13.75A13.75A15A
12.0A15.0A15.0A15A
13.5A16.875A16.875A20A
14.5A18.125A18.125A20A
15.0A18.75A18.75A20A

OCPD Voltage Rating

The OCPD must be rated for at least the maximum circuit voltage per NEC 690.7:

System TypeMaximum VoltageRequired OCPD Voltage Rating
Residential (1-2 family)600V DC600V DC minimum
Commercial/other1000V DC1000V DC minimum
Listed 1500V systems1500V DC1500V DC minimum

Using a 600V-rated fuse in a 1000V DC system is a code violation — the fuse may not safely interrupt fault current at 1000V.

When OCPD Can Be Omitted (690.9(B))

NEC 690.9(B) allows omitting source circuit overcurrent protection when:

  1. The circuit has only one module or one series string, AND
  2. The maximum current of all other source circuits connected to that conductor does not exceed the conductor’s ampacity

In practice, this applies to single-string single-inverter systems where the inverter is the only load and the string current never exceeds the conductor’s derated ampacity without an additional OCPD. Many modern microinverter and single-string string inverter systems meet this condition.

Check the inverter installation instructions — most manufacturers specify whether an external source circuit OCPD is required or whether the inverter’s internal protection is sufficient.

OCPD Omission Is Inverter-Specific

The conditions for omitting source circuit OCPDs depend on the specific inverter listing and installation instructions. Do not assume OCPD can be omitted without confirming with the inverter manufacturer’s documentation and the AHJ. Some AHJs require source circuit OCPDs regardless of the inverter listing — ask before omitting.

Combiner Box Fuse Selection

A combiner box aggregates multiple source circuits. Each input requires a listed DC fuse:

Combiner fuse rating per string:

  • String fuse minimum = 1.25 × module Isc
  • String fuse maximum = conductor ampacity of the string source circuit wire

Example: 4-string combiner, 9.58A Isc modules

  • Minimum fuse: 1.25 × 9.58A = 11.975A → use 12A or 15A DC fuse
  • String wire: 10 AWG THWN-2 (but check derated ampacity for the location)
  • Maximum fuse: cannot exceed derated conductor ampacity

Combiner output circuit:

  • Output circuit Isc = 4 strings × 9.58A = 38.32A
  • Minimum output OCPD: 1.25 × 38.32A = 47.9A → use 50A DC-rated breaker or fuse
  • Output circuit wire must be rated ≥ 50A derated ampacity

Listed PV Fuse Products

Common listed DC fuses for PV combiners:

  • Littelfuse KLKD, KLLU series (600V DC, 1A–30A)
  • Mersen (Ferraz Shawmut) PV series (600V, 1000V DC)
  • Eaton/Bussmann PV series (600V, 1000V DC)
  • Midnite Solar MNPV fuses (various ratings)

All must be installed in fuse holders listed for DC use at the applicable voltage. Standard AC fuse holders are not acceptable for DC circuits.

Generate OCPD Schedules Automatically

SurgePV creates complete OCPD schedules — source circuit fuses, combiner outputs, and inverter disconnects — sized per NEC 690.9 and included in every permit package.

Book a Demo

No commitment required · 20 minutes · Live project walkthrough

Frequently Asked Questions

What does NEC 690.9 require for OCPD sizing?

Minimum OCPD rating = 1.25 × maximum circuit current. For source circuits, that’s 1.25 × module Isc. For output circuits with multiple parallel strings, it’s 1.25 × (sum of all string Isc values). The OCPD must also be rated for the DC voltage of the circuit.

Can I use AC circuit breakers in DC solar circuits?

No. DC arcs don’t self-extinguish like AC arcs do. Standard AC breakers are not listed for DC interrupting duty at solar voltages. All OCPDs in PV source and output circuits must be specifically listed for DC operation at the applicable system voltage.

When can I omit overcurrent protection for a solar source circuit?

NEC 690.9(B) allows omitting source circuit OCPDs when the conductor is inherently protected by the maximum available fault current — typically in single-string systems where the conductor ampacity exceeds the maximum current that can flow. Verify with the inverter manufacturer’s installation instructions and confirm with the AHJ before omitting.

About the Contributors

Author
Rainer Neumann
Rainer Neumann

Content Head · SurgePV

Rainer Neumann is Content Head at SurgePV and a solar PV engineer with 10+ years of experience designing commercial and utility-scale systems across Europe and MENA. He has delivered 500+ installations, tested 15+ solar design software platforms firsthand, and specialises in shading analysis, string sizing, and international electrical code compliance.

Editor
Keyur Rakholiya
Keyur Rakholiya

CEO & Co-Founder · SurgePV

Keyur Rakholiya is CEO & Co-Founder of SurgePV and Founder of Heaven Green Energy Limited, where he has delivered over 1 GW of solar projects across commercial, utility, and rooftop sectors in India. With 10+ years in the solar industry, he has managed 800+ project deliveries, evaluated 20+ solar design platforms firsthand, and led engineering teams of 50+ people.

OCPD sizingsolar fuse sizingNEC 690.9solar breakercombiner box

Solar Compliance Updates in Your Inbox

Join 2,000+ solar professionals. Regulatory changes, code updates, and design tips — weekly.

No spam · Unsubscribe anytime