🇺🇸 United States Tool 8 min read

Solar Conductor Sizing Calculator: NEC 690.8 Ampacity Guide

Size DC solar conductors per NEC 690.8 with this step-by-step guide and reference tables. Covers the 125% continuous load factor, rooftop temperature derating (22°C adder), and conduit fill derating with worked examples.

Rainer Neumann

Written by

Rainer Neumann

Content Head · SurgePV

Keyur Rakholiya

Reviewed by

Keyur Rakholiya

CEO & Co-Founder · SurgePV

Published ·Last reviewed ·Regulator: NFPA / National Electrical Code (NEC)

NEC 690.8 is the conductor sizing section — and it requires three separate calculations stacked on top of each other. The 125% continuous load factor gets the most attention, but the rooftop temperature derating and conduit fill derating can be equally significant in hot climates.

The Three-Step 690.8 Calculation

Required ampacity = (Isc × 1.25) ÷ Temperature factor ÷ Fill factor

Step 1: Isc × 1.25

Solar is a continuous load — it can produce near-maximum current for 3+ hours. NEC requires conductors serving continuous loads to be sized at 125% of actual current.

Module Isc× 1.25 Required Ampacity
8.0A10.0A
9.58A11.975A
10.0A12.5A
11.5A14.375A
13.0A16.25A
14.5A18.125A

Step 2: Temperature Correction (NEC Table 310.15(B)(1)(1))

For rooftop conduit: effective temperature = maximum air temperature + 22°C

Temperature correction factors for 90°C (THWN-2) conductors:

Effective TemperatureCorrection Factor
≤30°C (86°F)1.00
31–35°C (87–95°F)0.96
36–40°C (97–104°F)0.91
41–45°C (105–113°F)0.87
46–50°C (114–122°F)0.82
51–55°C (123–131°F)0.76
56–60°C (132–140°F)0.71
61–65°C (141–149°F)0.65
66–70°C (150–158°F)0.58
71–75°C (159–167°F)0.50

Rooftop conduit effective temperatures by city:

CityMax Air Temp+ 22°CEffective TempCorrection Factor
Miami, FL33°C+ 22°C55°C0.76
Los Angeles, CA38°C+ 22°C60°C0.71
Phoenix, AZ43°C+ 22°C65°C0.65
Las Vegas, NV42°C+ 22°C64°C0.65
Atlanta, GA36°C+ 22°C58°C0.71
Dallas, TX40°C+ 22°C62°C0.65
Denver, CO36°C+ 22°C58°C0.71
New York, NY33°C+ 22°C55°C0.76
Boston, MA32°C+ 22°C54°C0.76
Seattle, WA29°C+ 22°C51°C0.82
Chicago, IL34°C+ 22°C56°C0.76

Step 3: Conduit Fill Derating (NEC Table 310.15(C)(1))

Conductors in ConduitDerating Factor
1–31.00 (no derating)
4–60.80
7–90.70
10–200.50

Both positive and negative conductors count. 2 strings in one conduit = 4 conductors → 0.80 derating.

Worked Examples

Single String, Phoenix Rooftop

Module Isc: 9.58A, Location: Phoenix, 1 string in conduit

Step 1: 9.58 × 1.25 = 11.975A
Step 2: 11.975 / 0.65 = 18.42A (conduit on Phoenix roof)
Step 3: 1.00 (single string = 2 conductors, no fill derating)
Required: 18.42A

From NEC Table 310.16 (90°C column): 12 AWG = 30A ✓ (sufficient)

Two Strings, Same Phoenix Conduit

2 strings (4 conductors), same conduit, Phoenix

Step 1: 9.58 × 1.25 = 11.975A (per string)
Step 2: 11.975 / 0.65 = 18.42A
Step 3: 18.42 / 0.80 = 23.03A (fill derating for 4 conductors)
Required: 23.03A per string circuit conductor

12 AWG (30A at 90°C table) — still sufficient.

High-Current Module, Miami Rooftop

Module Isc: 14.0A, Miami, 3 strings in one conduit (6 conductors)**

Step 1: 14.0 × 1.25 = 17.5A
Step 2: 17.5 / 0.76 = 23.03A (Miami rooftop effective 55°C)
Step 3: 23.03 / 0.80 = 28.79A (6 conductors, factor 0.80)
Required: 28.79A

From NEC Table 310.16 (90°C): 10 AWG = 40A ✓. 12 AWG (30A) would fail.

Terminal Temperature Limitation

If inverter input terminals are only rated for 75°C (check the inverter spec sheet), you must use the 75°C column in NEC Table 310.16 even for THWN-2 (90°C rated) wire. 10 AWG at 75°C = 35A. This is a common oversight on Phoenix-area installations where the 90°C column barely passes but the 75°C column does not.

NEC Table 310.16 Reference (Copper, 90°C, in Conduit)

AWGAmpacity (90°C column)Ampacity (75°C column)
1425A20A
1230A25A
1040A35A
855A50A
675A65A
495A85A
2130A115A
1/0170A150A

Automate NEC 690.8 Conductor Sizing

SurgePV calculates conductor ampacity automatically for every circuit — 125% factor, rooftop temperature derating, conduit fill — and exports the sizing table in your permit package.

Book a Demo

No commitment required · 20 minutes · Live project walkthrough

Frequently Asked Questions

How do I size solar DC conductors under NEC 690.8?

Three steps: (1) Isc × 1.25. (2) Divide by temperature correction factor (add 22°C to air temp for rooftop conduit). (3) Divide by conduit fill derating factor (4–6 conductors = 0.80). Select conductor from NEC Table 310.16 that meets the result.

What is the 22°C rooftop adder?

NEC 310.15(B)(3)(c) requires adding 22°C to the maximum air temperature for conductors in conduit within 7 inches of the roof surface. Phoenix rooftop conduit, for example, sees an effective conductor temperature of 65°C, requiring a 0.65 correction factor that substantially reduces allowable ampacity.

Does fill derating apply to a single-string conduit?

No. Fill derating only applies when more than 3 current-carrying conductors share a conduit. A single-string source circuit has 2 conductors (positive and negative) — no fill derating required.

About the Contributors

Author
Rainer Neumann
Rainer Neumann

Content Head · SurgePV

Rainer Neumann is Content Head at SurgePV and a solar PV engineer with 10+ years of experience designing commercial and utility-scale systems across Europe and MENA. He has delivered 500+ installations, tested 15+ solar design software platforms firsthand, and specialises in shading analysis, string sizing, and international electrical code compliance.

Editor
Keyur Rakholiya
Keyur Rakholiya

CEO & Co-Founder · SurgePV

Keyur Rakholiya is CEO & Co-Founder of SurgePV and Founder of Heaven Green Energy Limited, where he has delivered over 1 GW of solar projects across commercial, utility, and rooftop sectors in India. With 10+ years in the solar industry, he has managed 800+ project deliveries, evaluated 20+ solar design platforms firsthand, and led engineering teams of 50+ people.

conductor sizing calculatorNEC 690.8solar wire sizingampacity deratingsolar tools

Solar Compliance Updates in Your Inbox

Join 2,000+ solar professionals. Regulatory changes, code updates, and design tips — weekly.

No spam · Unsubscribe anytime