AC Size Calculator

AC Size Calculator for Solar Systems

Size AC breakers, disconnects, and conductors for solar inverter output. NEC-compliant calculations for residential and commercial solar interconnections.

About This Tool

Why Use This AC Size Calculator?

Properly sizing the AC side of a solar installation is critical for code compliance and safety. This calculator handles the NEC requirements so you can quickly determine the right breaker, wire gauge, and busbar compliance for any residential or commercial solar interconnection.

NEC 690.8 Compliance

Applies the 125% continuous load multiplier to inverter maximum output current for proper overcurrent protection device (OCPD) sizing.

Busbar Backfeed Check

Verifies the solar breaker meets NEC 705.12(B)(3) — the 120% busbar rule that limits total source ratings on a panel’s busbar.

Conductor Sizing

Recommends minimum wire gauge for the AC output circuit based on OCPD rating and NEC ampacity tables.

When to Use

When Do You Need an AC Size Calculator?

Every grid-tied solar installation requires proper AC-side sizing for code compliance and safety. Use this calculator when:

Inverter Interconnection Design

Size the AC breaker, disconnect, and conductors for the inverter output circuit. Every solar permit requires these calculations documented on the plan set.

120% Busbar Rule Compliance

Before committing to a panel location, verify the main panel can accept the solar backfeed breaker under NEC 705.12(B)(3). This calculator checks instantly.

Panel Upgrade Decisions

If the 120% rule fails, determine whether a main breaker derate, line-side tap, or full panel upgrade is the best path forward for the installation.

How to Use

How to Use the AC Size Calculator

1
Enter Inverter AC Output Current

Enter your inverter’s maximum AC output current (found on the inverter nameplate or datasheet).

2
Select AC Voltage

Select the AC voltage — 240V single-phase for residential, 208V or 480V three-phase for commercial.

3
Enter Panel Busbar Rating

Enter the main panel busbar rating (typically 100A, 150A, or 200A for residential).

4
Enter Main Breaker Size

Enter the existing main breaker size to check the 120% busbar rule.

5
Review Results

Review the recommended breaker size, wire gauge, and busbar compliance status.

Understanding Results

What Your Results Mean

Required OCPD Rating

The minimum breaker or fuse size for the solar AC circuit — always ≥125% of maximum inverter output current per NEC 690.8(A)(1).

Standard Breaker Size

The next standard breaker size up from the calculated minimum (15A, 20A, 25A, 30A, 40A, etc.).

120% Busbar Rule

Total of all breaker ratings (main + solar backfeed) must not exceed 120% of the busbar rating. If it fails, you may need a main breaker derate, line-side tap, or panel upgrade.

Minimum Wire Size

The AWG conductor size required based on the OCPD rating and NEC 310.16 ampacity tables.

Maximum AC Output

The maximum solar AC power that can be connected to this panel under NEC 705.12(B)(3).

Methodology

How We Calculate AC Sizing

This calculator follows National Electrical Code (NEC) requirements for sizing solar AC interconnection components. All calculations are based on the most current NEC standards.

NEC 690.8(A)(1): Solar OCPD ≥ Inverter max continuous output current × 1.25
NEC 240.6(A): Standard OCPD sizes — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100A...
NEC 705.12(B)(3) — 120% Rule: Main breaker + Solar breaker ≤ Busbar rating × 1.20
Maximum solar breaker = (Busbar × 1.20) - Main breaker
Conductor sizing: Per NEC 310.16 based on OCPD rating (not load current)
Line-side connections: Per NEC 705.12(A) — no busbar limit applies

Worked example: A SolarEdge SE7600H inverter outputs 31.7A maximum at 240V. NEC 690.8(A)(1): 31.7A × 1.25 = 39.6A minimum OCPD → standard 40A breaker. With a 200A busbar and 200A main breaker: (200 × 1.20) − 200 = 40A maximum solar breaker. This installation passes. Minimum conductor: #8 AWG copper per NEC 310.16.

Calculations sourced from SurgePV’s AC Size Calculator — surgepv.com/tools/ac-size-calculator/

Reference

Solar Inverter to Breaker Size Quick Reference

Common residential inverter sizes with corresponding NEC-compliant breaker and wire requirements at 240V single-phase.

Inverter SizeMax AC Current125% (NEC)Breaker SizeMin Wire (Cu)
3.8 kW15.8A19.8A20A#12 AWG
5.0 kW20.8A26.0A30A#10 AWG
6.0 kW25.0A31.3A35A#8 AWG
7.6 kW31.7A39.6A40A#8 AWG
10.0 kW41.7A52.1A60A#6 AWG
11.4 kW47.5A59.4A60A#6 AWG
15.0 kW62.5A78.1A80A#4 AWG
20.0 kW83.3A104.2A110A#2 AWG

120% Busbar Rule — Maximum Solar Breaker by Panel

Busbar RatingMain Breaker120% LimitMax Solar BreakerMax Solar System
100A100A120A20A~3.8 kW
125A125A150A25A~5.0 kW
150A150A180A30A~6.0 kW
200A200A240A40A~7.6 kW
200A175A (derated)240A65A~12.5 kW
225A200A270A70A~13.4 kW
Pro Tips

Common AC Sizing Mistakes to Avoid

Forgetting the 125% Continuous Load Factor

Solar inverters are continuous loads per NEC. The OCPD must be rated at 125% of maximum output current. A 31.7A inverter output needs a 40A breaker, not a 35A.

Not Checking the 120% Rule Before Site Visit

Discovering the 120% rule fails after contract signing creates costly change orders. Always verify the main panel’s busbar rating and main breaker size during the initial assessment.

Main Breaker Derate as a Simple Fix

If the 120% rule fails, replacing a 200A main breaker with a 175A or 150A breaker is often the cheapest solution. This frees up 25–50A of solar backfeed capacity without a panel upgrade.

Consider Line-Side Tap for Large Systems

A line-side (supply-side) connection per NEC 705.12(A) bypasses the 120% rule entirely. It connects before the main breaker, allowing any size solar system. Requires utility approval in most jurisdictions.

FAQ

Frequently Asked Questions

NEC 705.12(B)(3) states that the sum of the main breaker and all solar backfeed breakers must not exceed 120% of the panelboard busbar rating. For a 200A busbar with a 200A main breaker, the maximum solar breaker is (200 × 1.20) - 200 = 40A.

A 7.6kW inverter at 240V outputs 31.7A maximum. Multiply by 1.25 (NEC continuous duty) = 39.6A. The next standard breaker size is 40A. Your AC circuit needs a 40A breaker with #8 AWG copper conductors minimum.

You have several options: (1) Derate your main breaker — replace a 200A main with a 175A main to free up backfeed capacity. (2) Use a line-side tap connection before the main breaker — this bypasses the 120% rule entirely. (3) Upgrade to a larger busbar panel.

Yes, but the 120% rule still applies to the sub-panel’s busbar rating. The solar breaker must also be at the opposite end from the feeder breaker. Some jurisdictions require the solar connection at the main panel.

Wire size is based on the OCPD rating, not the actual current. A 40A solar breaker requires #8 AWG copper (NEC 310.16, 75°C column). A 30A breaker requires #10 AWG copper. Always verify with local code requirements.

NEC 690.13 requires a readily accessible disconnect means. Most jurisdictions require an AC disconnect between the inverter and the main panel. Some allow the backfeed breaker itself as the disconnect if it’s readily accessible.

Win your next project in just minutes.

Connect with a specialist for personalized insights and support tailored to your solar business needs.
Book Demo
UX designer