Back to Blog
solar design26 min read

Solar Racking Grounding: UL 2703 and NEC 690.43

Solar racking grounding explained: review UL 2703 compatibility, bonding paths, conductor decisions, and inspection records before installation.

Keyur Rakholiya

Written by

Keyur Rakholiya

CEO & Co-Founder · SurgePV

Rainer Neumann

Edited by

Rainer Neumann

Editorial contributor · SurgePV

Published ·Updated

Answer

Solar racking grounding starts with a documented bonding path through the approved module and mounting combination. The deciding factor is the manufacturer’s installation instructions and applicable electrical code, not a universal washer or wire size. Trace each array section to its equipment grounding connection and have conductor choices reviewed before construction.

Last updated: November 2026

A bonding drawing should let an installer trace the electrical connection from each module frame through the racking to the equipment grounding conductor. A rail gap, substituted clamp, or missing connection can interrupt that path even when the mechanical installation looks complete. This guide explains what to document and what to take back to the manufacturer or electrical designer before installation.

SurgePV publishes this post and sells solar design software.

Make the racking handoff easier to review

Use SurgePV array layouts and bill-of-materials output to organize the design information your electrical reviewer needs.

Book a Demo

Checking cost first? See the SurgePV pricing page.

Why Racking Bonding and Grounding Details Get Missed

Bonding details can be missed when electrical drawings and racking instructions describe different versions of the same array. The practical fix is to identify the exact hardware and trace its approved bonding path before work starts.

A commercial rooftop can contain many separate connections: module clamps, rail splices, jumpers, and conductor terminations. A drawing that labels the whole array as grounded without showing the connections leaves the crew to decide how these pieces fit together. Keep the electrical detail tied to the racking layout revision and the bill of materials.

No inspection dataset is supplied here, so this guide does not rank bonding defects by frequency or attach failure percentages to them. Instead, use the checks below as a project review sequence. A successful continuity check also cannot replace the required inspection of hardware, torque, corrosion protection, and compatibility.

The applicable rules depend on jurisdiction. The National Electrical Code (NEC) discussion here concerns projects using that code; it is not a substitute for India’s electrical rules or another country’s installation requirements. Ask the authority having jurisdiction (AHJ) which edition and local amendments apply.

The handoff also involves different skills. A racking installer understands mechanical assembly, while the electrical designer determines conductor routes and protection. Put both on the same drawing review so a mechanically complete row is not mistaken for an electrically complete system.

Bonding vs Grounding: The Critical Distinction

Bonding joins conductive parts into an intentional electrical path. Grounding connects a system or conductive part to earth. Treating those functions as interchangeable can hide a missing equipment grounding connection.

Bonding connects exposed metal parts such as module frames and rails through approved hardware. The goal is electrical continuity across the assembled equipment, including locations where the array changes direction or stops at an access aisle.

An equipment grounding conductor (EGC) is part of the equipment fault-current path. A grounding electrode conductor (GEC) connects to the grounding electrode system. A ground rod and soil are not substitutes for the required equipment fault-current path. Have the responsible electrical designer identify both functions on the drawing.

For a rail-mounted array, review the path in this order:

  1. Identify how each module frame bonds to its supporting hardware.
  2. Identify which rail splices carry a listed bonding function.
  3. Mark any breaks requiring a separate bonding connection.
  4. Show the EGC termination and route to the associated electrical equipment.
  5. Coordinate that route with the building’s grounding and protection design.

Why an incomplete equipment grounding path matters

If an exposed metal part becomes energized by damaged wiring, the protective system must respond as designed. A missing connection may leave the protection unable to operate as intended. Do not assume that physical contact between metal parts, or contact with earth, provides the required path.

A continuity measurement can help assess an installation, but an apparently low reading does not prove that the hardware is approved for long-term outdoor use. Verify the connection method and assembly instructions as well as the measurement procedure. Only qualified personnel should perform electrical checks under the project’s safe-work process.

Why inverter grounding arrangements matter

The grounding arrangement of the DC conductors is distinct from bonding the exposed metalwork. Inverter topology and protective functions affect the circuit design. Read the inverter documentation rather than assuming that a transformerless system follows the same arrangement as a legacy inverter.

Keep the inverter’s grounding instructions in the electrical design package. Identify the designated terminals and any restrictions on external bonding. Do not add a DC conductor-to-earth connection merely because the racking itself needs an equipment grounding connection.

UL 2703 Listing: What It Actually Covers

UL 2703 addresses PV mounting systems and related bonding hardware. The useful question is whether the certification covers the actual module, mounting configuration, and components on your project.

Per UL Solutions’ PV mounting certification overview, checked November 2026, the standard includes mounting devices, clamps and ground lugs for ground-mounted and roof systems. UL also describes rooftop fire classification as applying to the module and racking combination.

UL 2703
PV mounting standard
Module + rack
Rooftop fire classification basis
Integrated
IronRidge UFO bonding method

Source: the UL overview above and IronRidge’s UFO product documentation below, opened November 2026. These are scope facts, not a comparison of electrical ratings.

Document or component What the source describes What to verify for the project
UL mounting certification overview Mounting devices, clamps and ground lugs Actual certification scope and equipment combination
Rooftop system fire classification Module and racking combination Roof configuration and applicable assembly details
IronRidge UFO product page Integrated module-to-rail bonding Compatible module, rail and installation instructions

Key Takeaway

A certification label is the start of the review. Keep the applicable module compatibility record and installation instructions with the actual hardware schedule.

What the listing covers and does not cover

Review the rail or mounting system, clamp assembly, module frame, and bonding components together. A certificate for a product family does not justify every possible combination of those parts. Check the scope that applies to the delivered model numbers.

If procurement proposes a substitute clamp or module, stop that substitution from reaching the roof until someone has checked the documentation. Adding an improvised jumper is not a general remedy for an incompatible mechanical assembly or missing certification.

Reading the installation manual properly

The installation and operation manual (IOM) should be checked for permitted components, clamp positions, tightening instructions, grounding connections, and any limits on reuse. Record its revision and keep it with the construction drawing.

Where the manual and approved drawing appear to disagree, obtain a written resolution from the responsible designer and manufacturer, involving the AHJ where required. A manual does not give an installer permission to disregard an inspector’s decision or local requirements.

Pro Tip

Before procurement, save the applicable manual and compatibility record with the approved bill of materials. Repeat that check when a module, rail, clamp, or splice changes.

WEEB Clips: How They Work & When You Need One

A bonding washer is needed when the selected mounting assembly specifies it. Other assemblies use integrated bonding hardware, so adding a separate washer by habit can be just as inappropriate as leaving a required one out.

WEEB is a product-family name associated with bonding washers and related hardware. In a specified assembly, contact features penetrate surface coatings to create the intended electrical connection. The geometry, material, placement, and tightening procedure matter; visual similarity is not enough to establish interchangeability.

When you need a WEEB

Read the installation detail for the exact clamp position. It should identify the part, its orientation, and the surfaces it contacts. Check end clamps and mid-clamps separately rather than assuming the same detail applies everywhere.

An integrated bonding clamp or approved bonding splice may provide the required connection without a separate washer. That conclusion must come from the selected system’s instructions, not from a rule that all modern racking works the same way.

Choosing the right variant

Specify the complete manufacturer part number on the material schedule. Ask the supplier to show how it matches the mounting detail, especially when a catalog offers several similar-looking washers or lugs. Do not carry a hardware recommendation from one manufacturer’s rail to another.

At receipt, compare the packaging and the actual components with the approved schedule. Set aside unapproved substitutions. This check is easier before the crew has distributed parts across the roof, and it leaves a clear record for whoever resolves the mismatch.

Reassembly Check

After a clamp is removed, check the manufacturer’s replacement or reuse instructions for every bonding component. Do not assume that a previously compressed contact can be used again.

Integrated Grounding Lay-in Lugs vs Separate Lugs

A lug terminates a conductor; a bonding clamp joins equipment parts. Choose both through the approved assembly details rather than treating them as interchangeable grounding accessories.

Method 1: Separate lay-in lug

A separately mounted lug provides a conductor termination at a specified location. Check its conductor material, permitted size range, environmental rating, mounting hardware, and tightening instructions. A lug approved for one surface or conductor is not automatically suitable for another.

Do not drill a rail or module frame unless the relevant instructions permit the hole and location. Added holes can affect both mechanical performance and corrosion protection. Show the approved attachment detail in the drawing so the crew does not have to improvise.

Method 2: Combined bonding and conductor connection

Some assemblies combine a bonding interface and conductor termination. Review the complete assembly drawing, including any washers, bolts, or surface preparation. A combined component still needs a suitable connection to the equipment and the correct conductor termination.

Check that maintenance can reach the termination without disturbing unsupported parts of the array. Label its location on the as-built drawing and preserve the applicable tightening instructions for later service.

Method 3: Integrated mounting-system bonding

A mounting system may carry bonding through specified clamps and splices. This can change the number and position of separate connections, but it does not eliminate the need to understand the complete equipment grounding route.

Which method to use

Choose the approved method for the selected hardware and layout. Evaluate assembly clarity, accessibility, supplier support, and maintenance needs. There is no universal labor saving or hardware-cost percentage that applies to every roof.

A useful procurement comparison includes the full installed assembly, not just the price of a lug. Count required fasteners, conductor terminations, access constraints, and replacement parts, then obtain project quotes. Keep this commercial comparison separate from the electrical suitability review.

Module Frame to Rail Bonding: NEC 690.43 & UL 2703 Path

The frame-to-rail connection must follow the approved equipment combination and applicable electrical rules. Check the standard and locally adopted edition for the installation; this guide does not reproduce a code clause or set a universal conductor size.

What this means in practice

Mark which components provide the frame-to-rail bond. The drawing should identify the module model, clamp, rail, and applicable installation detail. Give installers enough information to distinguish a mechanical attachment from a component with a bonding function.

If the equipment combination is not supported by the available documentation, obtain an approved design resolution before installation. A separate jumper may be part of an engineered solution, but it cannot by itself resolve incompatible clamps, unsupported module loading, or missing fire-classification evidence.

Checking the adopted code edition

Do not assume a project uses a code simply because its publication year matches the installation year. Record the edition adopted by the jurisdiction, the applicable amendments, and the plan review conditions.

No verified comparison of NEC edition changes is provided here. Have the responsible electrical designer check the standard for the bonding arrangement and document the requirements that govern this project. Preserve that decision with the permit record so field personnel do not work from an unsupported paraphrase.

Rail-to-Rail Bonding: When You Need a Jumper

A separate jumper is needed where the approved bonding design requires one. A physical rail gap is a reason to inspect the path, not proof that a particular jumper detail is always required.

A mounting system may carry bonding through specified rail splices, module connections, or dedicated conductors. Trace each permitted route against the actual layout. Do not assume every module bridges rails electrically or that every metal splice carries a bonding function.

Review aisle gaps, disconnected subarrays, rail expansion joints, and maintenance access cuts. Also consider what happens when a module is removed for service. The design and maintenance instructions should explain how required connections are maintained or restored.

Jumper sizing

Have the electrical designer select the conductor or listed bonding device for the circuit and installation conditions. Check the standard, equipment instructions, conductor material, and terminal limits. Avoid an inventory-wide rule that one wire size is suitable for every project.

A jumper detail should show both termination points, routing, support, and any movement allowance required by the assembly. Keep it clear of sharp edges and locations where future maintenance could damage it. Record any change from the approved detail before concealment.

Pro Tip

Mark required bonding connections on the installation drawing as well as the bill of materials. Give each location a reference that can be matched to a close-out photograph.

EGC Sizing per NEC 690.45 and Table 250.122

EGC sizing is a circuit-specific electrical design task. Check the standard and adopted edition with the responsible designer rather than copying a wire-size table into every array package.

Start by identifying the circuit, protection arrangement, conductor material, and equipment instructions. A protective device elsewhere in the plant is not automatically the governing input for every equipment grounding conductor. Separate the DC source circuits, combined circuits, and AC output circuits in the schedule.

Design record Information to include Review purpose
Circuit identification Start point, end point and drawing reference Avoid applying one size across unrelated circuits
Protection basis Applicable protective device or design calculation Support the conductor-selection decision
Installation conditions Material, route, exposure and physical protection Check suitability beyond nominal wire size
Termination detail Lug model and conductor compatibility Match the selected conductor to actual hardware

This is a documentation checklist, not an ampacity or code table. The equipment-specific scope follows the UL and manufacturer sources cited above; the circuit selection needs project engineering.

Do not assume a conductor reduction is available

A reduced conductor size needs a valid basis in the applicable rules and design. Do not reduce an EGC simply because a rough estimate of available fault current appears low. Ask the designer to record the governing calculation and any conditions attached to the selection.

Where the EGC runs

Show the intended route to the associated equipment grounding terminal and coordinate it with the circuit conductors. Identify transitions through junction boxes, combiners, and inverter equipment. The route must remain understandable where the array divides into separate sections.

For ground-mounted arrays, coordinate the route with trench and foundation drawings. For rooftops, coordinate it with access paths and roof penetrations. Keep conductor support and physical protection visible in the details rather than leaving them as field assumptions.

Carry the layout into the electrical review

Bring a project to a SurgePV walkthrough to see its electrical workflow support and bill-of-materials output.

Book a Demo

Checking cost first? See the SurgePV pricing page.

Racking Manufacturer Specifics: IronRidge, Unirac, S-5!, K2, Schletter

Manufacturer instructions govern the hardware details for their systems. Use a product-specific comparison rather than assigning one bonding method to an entire brand.

IronRidge

IronRidge’s UFO page describes the clamp as part of its integrated grounding system and says it bonds modules to XR rails. Do not add a separate bonding washer simply because it appears in another racking system’s detail. Check the applicable assembly instructions for your module and rail combination.

The IronRidge pitched-roof product library also identifies the BOSS bonded structural splice. Its presence illustrates why a generic rule about jumpers at all rail joints is insufficient. Verify which splice and rail assembly your project actually uses. Sources opened November 2026.

Unirac

Request the documentation for the proposed system, including module compatibility and electrical bonding details. Do not assume a detail from one Unirac family applies to another. The material schedule should use the same system name as the drawings.

S-5!

For a proposed metal-roof attachment, request the exact roof-profile, attachment, and module-mounting documentation. Roof attachment suitability and electrical bonding are separate checks. Avoid treating a brand name as approval for every roof seam or profile.

K2 Systems

Identify the market and specific mounting product before reviewing bonding details. Request the installation instructions applicable to the supplied system. Resolve whether separate components are required at connections and splices through that documentation.

Schletter

Use the project-specific mounting-system details and component schedule. Ground-mount and rooftop drawings may have different interfaces and service conditions. Check that the bonding layout follows the supplied assembly rather than a detail copied from another project.

Illustrative Design Example

Suppose a crew receives a bonding component with a different part number from the approved schedule. Quarantine the substitute and ask the designer and manufacturer to resolve compatibility before installation. This is a hypothetical handoff example, not a reported project.

Field Inspection: AHJ Common Pushbacks

Prepare the inspection package around the approved design and the installed equipment. The items below are practical checks, not a ranked dataset of inspection failures.

Pushback 1: Missing or wrong bonding component

Compare the installed part with the approved detail. Check the required orientation and contact surfaces before modules obscure the connection. Photograph the detail and retain packaging or part identification where it helps establish what was installed.

If the component cannot be identified, ask the manufacturer for assistance. Do not declare a connection acceptable solely because it looks similar to the drawing.

Pushback 2: Unverified tightening procedure

Use the torque and method in the exact component instructions. A generic clamp-torque range can damage equipment or leave it incorrectly assembled. Record the tool, specified setting, and completion check through the installation quality process.

A paint mark can identify a checked fastener, but it does not prove the correct torque was applied. It should support the inspection record, not replace it.

Pushback 3: Unclear bonding across array breaks

Walk the path shown on the drawing through every separate row or subarray. Verify the approved splices and any required jumpers. If the field layout changed, update the drawing and obtain review before assuming the original bonding path still works.

Pushback 4: Conductor or terminal mismatch

Compare installed conductor material and size with the reviewed schedule and lug instructions. Check exposed markings and termination accessibility. Refer discrepancies to the electrical designer rather than substituting a larger conductor that may not fit the terminal.

Pushback 5: Missing grounding-electrode design information

Where the project requires electrode work, show its approved location and connection details. Coordinate inspection before the work is concealed. Obtain project-specific direction if the existing grounding system cannot be identified or differs from the design assumptions.

NEC 250.66 and 250.122: Sizing Bonding Conductors

Equipment grounding and grounding-electrode conductors serve different functions and need separate review. Check the standard for the applicable sizing method; do not use one conductor schedule for both by analogy.

Label the EGC and GEC distinctly on the electrical drawings. For each, identify the connection points and the reason for the selected conductor. Existing service grounding does not remove the need to review how new PV equipment connects into that system.

If a project includes service changes, a new separately derived system, or other unusual arrangements, involve the responsible electrical designer early. Record any assumptions about existing equipment and identify what the field survey must verify before construction.

Common Bonding and Grounding Mistakes

The recurring design risk is assuming a connection works without documenting its approved function. Use these checks in procurement, installation, and close-out.

1. Specified bonding component omitted

Check the applicable detail rather than expecting every clamp to contain a separate washer. Integrated assemblies and separate bonding parts need different visual checks. Give the crew a photograph or drawing of the approved configuration.

2. Generic hardware substituted

A flat washer or similar-looking clamp is not evidence of a suitable bonding path. Maintain the specified assembly and resolve substitutions before work proceeds. Preserve the written resolution with the material record.

3. Incompatible conductor and terminal materials

Check the lug’s permitted conductor materials, preparation instructions, and environmental suitability. Use joint compounds only where the applicable instructions call for them. Do not assume a compound can make incompatible materials acceptable.

4. Separate array section omitted

A second row or disconnected subarray needs its bonding route reviewed explicitly. Use the drawing to identify how that section connects to the equipment grounding system and whether service removal affects the path.

5. AC and DC conductor selections conflated

Review the inverter AC output and PV DC circuits separately. Their protection arrangements and terminal requirements may differ. Carry both decisions into the construction schedule rather than copying a conductor size between circuits.

Ground Rod and Supplemental Electrode Requirements

A ground-mounted array does not justify a universal ground-rod recipe. Electrode requirements depend on the electrical design, adopted rules, existing grounding system, and installation conditions.

Ask the electrical designer to identify whether electrode work is required, which arrangement applies, and how it connects to the equipment grounding system. Record any inspection or measurement requirements before trenching and foundation work begin.

Do not use a ground rod as a substitute for the required equipment grounding path. Likewise, do not specify rod dimensions, spacing, conductor size, or a resistance target from an unrelated project. Check the standard and approved design for those values.

For rooftop additions, establish how the new equipment connects to the existing system. If the existing grounding arrangement is inaccessible or uncertain, list the survey action needed to resolve it. A note saying “ground to existing” is not enough when nobody has identified the connection.

Using SurgePV Outputs in the Electrical Review

SurgePV supports array layout, electrical workflows, and bill-of-materials output. Those capabilities can help organize design information; they do not replace engineering review, equipment instructions, or approval by the AHJ.

Use the array layout workflow to organize the roof geometry and module positions that the electrical reviewer needs. Keep the approved racking schedule, bonding details, and conductor calculations linked to the same project revision.

Before purchasing software for a grounding-specific task, bring a sample requirement to the walkthrough. Ask how the output fits your existing drawing and review process. Do not assume automated selection of bonding hardware, code-table sizing, or faster permit approval unless that scope is agreed in writing.

Conclusion: Three Actions for Reliable Racking Bonding

Start with the approved equipment combination, draw the complete bonding route, and verify the installation against those records.

  1. Obtain the applicable mounting instructions and compatibility information before procurement. Resolve substitutions before the hardware reaches the roof.
  2. Mark the specified connections on the installation drawings. Include access gaps, separate subarrays, and conductor termination points.
  3. Complete the project inspection and close-out records, including revised drawings and any written manufacturer or designer decisions.

For related circuit planning, use the string sizing walkthrough. To see how the layout and material outputs fit your handoff, bring a racking project to a demo.

Frequently Asked Questions

What is the difference between bonding and grounding in solar racking?

Bonding joins conductive equipment parts; grounding connects a system or conductive part to earth. The equipment grounding path and grounding electrode connection have different functions and should be identified separately in the design.

What does UL 2703 cover for solar racking?

UL 2703 covers PV mounting systems and related devices, including bonding hardware and ground lugs. UL also uses it for rooftop system fire classification, which depends on the module and racking combination.

Do I need WEEB clips with every solar mounting system?

No, the required bonding components depend on the approved mounting assembly. Some systems use integrated bonding clamps; follow the exact installation instructions instead of adding or removing washers by habit.

How do I size an equipment grounding conductor for solar racking?

Have the electrical designer size it for the circuit, applicable code edition, and installation conditions. Check the standard and equipment terminal requirements rather than applying a generic array-wide wire size.

When does a solar rail need a bonding jumper?

A rail needs a separate jumper where the approved bonding design requires one. Review splices, gaps, disconnected subarrays, and maintenance conditions against the manufacturer instructions.

Can a ground rod replace the equipment grounding conductor?

No, a ground rod is not a substitute for the required equipment fault-current path. The electrical designer must specify both the equipment grounding arrangement and any required electrode work.

Where this fits

This article is part of SurgePV's Solar Design hub, which works through the topic from first principles to the decisions a project team actually has to make.

About the Contributors

Author
Keyur Rakholiya
Keyur Rakholiya

CEO & Co-Founder · SurgePV

Keyur Rakholiya is identified by SurgePV as its CEO and a company co-founder. His SurgePV author page lists only role information that can be tied to the public profile below; credentials, project totals, testing claims, media appearances, and speaking engagements are not asserted without retained evidence.

Editor
Rainer Neumann
Rainer Neumann

Editorial contributor · SurgePV

Rainer Neumann is credited as an editorial contributor on SurgePV content. This profile does not assert engineering credentials, project totals, software-testing experience, education, speaking engagements, or media citations because independent verification evidence is not retained in the publication record.

Get Solar Design Tips in Your Inbox

Join 2,000+ solar professionals. One email per week - no spam.

No spam · Unsubscribe anytime

Book Free Demo

Choose which optional technologies SurgePV may use. Essential storage remains active for security and requested features.